β¨ Electricity Reliability Statistics
17 NOVEMBER 2006 NEW ZEALAND GAZETTE, No. 141 4091
- The total number of faults per 100 circuit kilometres of overhead prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.
| Nominal Voltage | Lines Faults per 100 km | Cable Faults per 100 km | Total Faults per 100 km |
|---|---|---|---|
| 33 kv | 0.98 | 40.50 | 1.30 |
| 11 kv | 3.03 | 4.01 | 3.06 |
| TOTALS | 2.85 | 4.60 | 2.92 |
| Faults/100km | Faults/100km 33kV | Faults/100km 11kV | |
|---|---|---|---|
| Target 31/03/07 | 2.23 | 0.65 | 2.38 |
| 31/03/2007 Avg forecast | 2.23 | 0.65 | 2.38 |
| 31/03/2008 Avg forecast | 2.09 | 0.65 | 2.23 |
| 31/03/2009 Avg forecast | 2.09 | 0.65 | 2.23 |
| 31/03/2010 Avg forecast | 1.95 | 0.32 | 2.11 |
| 31/03/2011 Avg forecast | 1.95 | 0.32 | 2.11 |
8.12,16 The SAIDI, SAIFI, CAIDI for the total number of interruptions.
9,13,17 SAIDI targets for the following financial year for-
(a) Planned interruptions by the line owner (Class B); and
(b) Unplanned interruptions originating within the works of the line owner (Class C).
10,14,18 Average SAIDI targets for the following financial year and the subsequent 4 financial years for each of-
(a) Planned interruptions by the line owner (Class B); and
(b) Unplanned interruptions originating within the works of the line owner (Class C).
11,15,19 The SAIDI for the total number of interruptions within each interruption class.
| NETWORK OR GENERATION OWNER | DISC CLASS | CLASSIFICATION OF INTERRUPTIONS | SAIDI Numerator (Cust-min) | SAIDI Result (min/Conn Cust) | SAIFI Numerator (Cust-int) | SAIFI Result (Int/Conn Cust) | CAIDI Result (min/Cust int) |
|---|---|---|---|---|---|---|---|
| MainPower | B | Planned Shut-downs | 1,021,518 | 33.3056 | 4,749 | 0.1548 | 215.1017 |
| C + G | Unplanned Interruptions | 2,142,984 | 69.8694 | 46,683 | 1.5221 | 45.9046 | |
| Subtotal | 3,164,482 | 103.1751 | 51,432 | 1.6769 | 61.5275 | ||
| Trans Power | A | Planned Shut-downs | 0 | 0 | 0 | 0 | 0 |
| D | Unplanned Interruptions | 184,038 | 6.0004 | 5,169 | 0.1685 | 35.6042 | |
| Subtotal | 184,038 | 6.0004 | 5,169 | 0.1685 | 35.6042 | ||
| Other | G | Other Interruptions | 0 | 0 | 0 | 0 | 0 |
| E | Unplanned Interruptions | 0 | 0 | 0 | 0 | 0 | |
| Subtotal | 0 | 0 | 0 | 0 | 0 | ||
| TOTAL | 3,348,520 | 109.1754 | 56,601 | 1.8454 | 59.1600 |
Common Denominator = No of Cust. 30,671
| Class B | SAIDI | SAIFI | CAIDI |
|---|---|---|---|
| Target 31/03/07 | 52 | 0.32 | 162 |
| 31/03/2007 Avg forecast | 52 | 0.32 | 162 |
| 31/03/2008 Avg forecast | 38 | 0.25 | 152 |
| 31/03/2009 Avg forecast | 37 | 0.23 | 160 |
| 31/03/2010 Avg forecast | 35 | 0.21 | 166 |
| 31/03/2011 Avg forecast | 33 | 0.21 | 157 |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2006, No 141
Gazette.govt.nz —
NZ Gazette 2006, No 141
β¨ LLM interpretation of page content
π
Disclosure of Reliability Performance Measures
(continued from previous page)
π Trade, Customs & IndustryElectricity, Reliability, Interruptions, Performance Measures, Commerce Act, Disclosure Requirements