β¨ Electricity Reliability Performance
2 OCTOBER
NEW ZEALAND GAZETTE
3321
TAURANGA ELECTRICITY LIMITED
DISCLOSURE OF RELIABILITY PERFORMANCE MEASURES
TOTAL INTERRUPTIONS ABOVE 3.3kV
| CLASS | No. OF INTERR | DURATION FACTORS | CONNT CUST | TOTAL CUST | SAIDI | SAIFI | CAIDI |
|---|---|---|---|---|---|---|---|
| A | 1 | 0 | 0 | 4401.5 | 0 | 0 | 0 |
| B | 13 | 9798 | 101 | 4401.5 | 2.226 | 0.0229 | 97.0099 |
| C | 4 | 25546 | 314 | 4401.5 | 5.804 | 0.0713 | 81.3567 |
| D | 0 | 0 | 0 | 4401.5 | 0 | 0 | 0 |
| E | 0 | 0 | 0 | 4401.5 | 0 | 0 | 0 |
| F | 0 | 0 | 0 | 4401.5 | 0 | 0 | 0 |
| G | 0 | 0 | 0 | 4401.5 | 0 | 0 | 0 |
| TOTAL | 18 | 35344 | 415 | 4401.5 | 8.030 | 0.094 | 85.166 |
NUMBER OF FAULTS PER 100km AT PRESCRIBED VOLTAGE
| VOLTAGE | OVERHEAD LINES | UNDERGROUND CABLES | TOTAL |
|---|---|---|---|
| No of Faults | Length(km) | per 100km | |
| 33kV | 2 | 8.5 | 23.529 |
| 11kV | 1 | 1.66 | 60.241 |
| TOTAL | 3 | 10.16 | 29.528 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1996, No 138
NZLII —
NZ Gazette 1996, No 138
β¨ LLM interpretation of page content
π
Tauranga Electricity Limited Performance Measures and Statistics
(continued from previous page)
π Trade, Customs & IndustryPerformance Measures, Statistics, Tauranga Electricity Limited, Electricity Information Disclosure Regulations 1994, Financial Performance, Efficiency Performance, Energy Delivery Efficiency, Reliability Performance, Interruptions, Faults