β¨ Electricity Performance Statistics
NEW ZEALAND GAZETTE
No. 138
TAURANGA ELECTRICITY LIMITED
DISCLOSURE OF RELIABILITY PERFORMANCE MEASURES
TOTAL INTERRUPTIONS ABOVE 3.3kV
| CLASS | No. OF INTERR. | DURATION FACTORS | CONNT. CUST | TOTAL CUST | SAIDI | SAIFI | CAIDI |
|---|---|---|---|---|---|---|---|
| A | 0 | 0 | 0 | 4785 | 0 | 0 | 0.000 |
| B | 2 | 13200 | 55 | 4785 | 2.759 | 0.011 | 240.000 |
| C | 12 | 130634 | 2348 | 4785 | 27.301 | 0.491 | 55.636 |
| D | 1 | 64448 | 848 | 4785 | 13.469 | 0.177 | 76.000 |
| E | 0 | 0 | 0 | 4785 | 0 | 0 | 0.000 |
| F | 2 | 23880 | 296 | 4785 | 4.991 | 0.062 | 80.676 |
| G | 0 | 0 | 0 | 4785 | 0 | 0 | 0.000 |
| TOTAL | 17 | 232162 | 3547 | 4785 | 48.519 | 0.741 | 65.453 |
NUMBER OF FAULTS PER 100km AT PRESCRIBED VOLTAGE
| VOLTAGE | OVERHEAD LINES | UNDERGROUND CABLES | TOTAL | |||
|---|---|---|---|---|---|---|
| No of Faults | Length(km) | per 100km | No of Faults | Length(km) | per 100km | |
| 33kV | 0 | 8.5 | 0 | 0 | 9.25 | 0 |
| 11kV | 0 | 1.86 | 0 | 12 | 44.74 | 26.822 |
| TOTAL | 0 | 10.16 | 0 | 12 | 53.99 | 22.226 |