Electricity Reliability Performance




30 AUGUST 2005
NEW ZEALAND GAZETTE, No. 147
3627

Vector Limited
Electricity Lines Business

Reliability Performance Measures to be Disclosed by Disclosing Entities (Other Than Transpower)
For the year ended 31 March 2005

SCHEDULE 1 – PART 5

  1. Interruptions

    2005 2004 2003¹ 2002
    Total number of interruptions according to class
    Class A - 1 1 -
    Class B 416 610 329 26
    Class C 1,131 1,333 896 299
    Class D 7 7 6 6
    Class E - - - -
    Class F - - - -
    Class G - - - -
    Class H - - - -
    Class I - - - -
    Total interruptions 1,554 1,951 1,232 331
  2. Interruption targets

    2006
    (a) Planned (class B) 400
    (b) Unplanned (class C) 1,067
  3. Average interruption targets

    2006-2010
    (a) Planned (class B) 318
    (b) Unplanned (class C) 813
  4. The proportion (expressed as a percentage) of the total number of class C interruptions not restored within

    2005
    (a) 3 hours 26.4%
    (b) 24 hours 0.8%

¹ The 2003 performance statistics have been calculated using a time-weighted average in accordance with the Electricity (Information Disclosure) Regulations 2000, Regulation 33. Vector Limited was combined with UnitedNetworks Limited in October 2002. One month (October 2002) includes the Eastern region of UnitedNetworks Limited as well as the Northern and Wellington regions. The final 5 months are for Vector Limited, plus the Northern and Wellington regions of UnitedNetworks Limited.



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2005, No 147


Gazette.govt.nz PDF NZ Gazette 2005, No 147





✨ LLM interpretation of page content

🏭 Vector Limited's Reliability Performance Measures (continued from previous page)

🏭 Trade, Customs & Industry
Electricity, Reliability, Performance Measures, Interruptions, Vector Limited