✨ Electricity Reliability Performance Measures
24 AUGUST 2005 NEW ZEALAND GAZETTE, No. 140 3399
5 (b) and (d) Target number of faults per 100 circuit kilometres for next financial year
| 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|
| 66 kV | 3.0 | 2.0 | - | - |
| 33 kV | 5.0 | 3.0 | 2.5 | 2.5 |
| 11 kV | 12.5 | 12.5 | 12.0 | 10.0 |
| 6.6 kV | 7.0 | 6.0 | 6.0 | 4.0 |
| Total | 10.0 | 9.4 | 8.9 | 7.2 |
5 (c) and (d) Average target number of faults per 100 circuit kilometres for next 5 years
| 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|
| 66 kV | 3.0 | 2.0 | - | - |
| 33 kV | 5.0 | 3.0 | 2.5 | 2.5 |
| 11 kV | 12.5 | 12.5 | 12.0 | 10.0 |
| 6.6 kV | 7.0 | 6.0 | 6.0 | 4.0 |
| Total | 10.0 | 9.4 | 8.9 | 7.2 |
6 The total number of faults per 100 circuit kilometres of underground prescribed voltage electric line
| 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|
| 33 kV | 3.4 | 3.4 | 1.1 | 0.0 |
| 11 kV | 4.4 | 5.0 | 5.2 | 4.0 |
| 6.6 kV | 5.6 | 2.5 | 1.7 | 1.8 |
| Total | 4.7 | 3.9 | 3.2 | 2.4 |
7 The total number of faults per 100 circuit kilometres of overhead prescribed voltage electric line
| 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|
| 66 kV | 1.8 | 1.8 | - | - |
| 33 kV | 5.9 | 3.4 | 5.0 | 2.6 |
| 11 kV | 14.0 | 13.9 | 13.4 | 11.9 |
| 6.6 kV | 7.6 | 7.5 | 8.9 | 6.4 |
| Total | 11.2 | 10.8 | 11.0 | 9.1 |
8 The SAIDI for the total number of interruptions (minutes)
| 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|
| 80.5 | 97.3 | 101.3 | 88.7 |
9 SAIDI target for next financial year (minutes)
| Class | 2005 | 2004 | 2003 | 2002 |
|---|---|---|---|---|
| Class B – planned by line owners | 15.0 | 15.0 | 15.0 | 15.0 |
| Class C – unplanned by line owners | 75.0 | 75.0 | 75.0 | 75.0 |
10 Average SAIDI targets for next 5 years (minutes)
| Class | 2005 | 2004 | 2003 | 2002 |
|---|---|---|---|---|
| Class B – planned by line owners | 15.0 | 15.0 | 15.0 | 15.0 |
| Class C – unplanned by line owners | 75.0 | 75.0 | 75.0 | 75.0 |
11 The SAIDI for the total number of interruptions within each interruption class (minutes)
| Class | 2005 | 2004 | 2003 | 2002 |
|---|---|---|---|---|
| Class A – planned by Transpower | - | - | - | - |
| Class B – planned by line owners | 7.3 | 16.3 | 20.5 | 13.8 |
| Class C – unplanned by line owners | 73.2 | 80.0 | 68.6 | 61.5 |
| Class D – unplanned by Transpower | - | 1.0 | 12.1 | 13.4 |
| Class E – unplanned by embedded generation | - | - | 0.1 | - |
| Class F – unplanned by generation on other net-works | - | - | - | - |
| Class G – unplanned by other line owner | - | - | - | - |
| Class H – planned by another line owner | - | - | - | - |
| Class I – any other loss of supply | - | - | - | - |
LexisNexis
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2005, No 140
Gazette.govt.nz —
NZ Gazette 2005, No 140
✨ LLM interpretation of page content
🏭
Disclosure of reliability performance measures under requirement 21 of the Electricity Information Disclosure Requirements 2004
(continued from previous page)
🏭 Trade, Customs & IndustryElectricity, Reliability, Performance Measures, Faults, Interruptions