✨ Energy Performance Measures
HORIZON ENERGY DISTRIBUTION LIMITED
Requirement 21 Reliability Performance Measures (Continued)
For the year ended 31 March 2004
| 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|
| 12. | SAIFI for Total Number of Interruptions | 3.54 ¹ | 1.62 | 1.60 |
¹ Due to July 2004 flooding and other extreme weather events
| 2006 | 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|---|
| 13. | SAIFI Targets (Next Year) | ||||
| (a) | Planned interruptions (Class B) | 0.30 | 0.30 | 0.30 | 0.33 |
| (b) | Unplanned interruptions (Class C) | 1.50 | 1.50 | 1.50 | 1.30 |
| 2006 | 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|---|
| 14. | Average SAIFI Targets (Next 5 Years) | ||||
| (a) | Planned interruptions (Class B) | 0.30 | 0.30 | 0.30 | 0.33 |
| (b) | Unplanned interruptions (Class C) | 1.50 | 1.50 | 1.50 | 1.30 |
| 15. | SAIFI for Total Interruptions by Class |
| Class A - Transpower planned interruptions | 0.76 | 0.18 | 0.17 | 0.00 |
| Class B - Horizon planned interruptions | 0.11 | 0.16 | 0.18 | 0.22 |
| Class C - Horizon unplanned interruptions | 2.35 | 1.19 | 0.68 | 1.43 |
| Class D - Transpower unplanned interruptions | 0.16 | 0.19 | 0.36 | 0.90 |
| Class E - Horizon generation unplanned interruptions | 0.00 | 0.00 | 0.00 | 0.00 |
| Class F - Other generation unplanned interruptions | 0.07 | 0.00 | 0.00 | 0.00 |
| Class G - Other line owner unplanned interruptions | 0.09 | 0.00 | 0.00 | 0.00 |
| Class H - Other line owner planned interruptions | 0.00 | 0.00 | 0.00 | 0.00 |
| Class I - Not in A to H | 0.00 | 0.00 | 0.00 | 0.00 |
| 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|
| 16. | CAIDI for Total Number of Interruptions | 279 | 135 | 120 |
| 2006 | 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|---|
| 17. | CAIDI Targets (Next Year) | ||||
| (a) | Planned interruptions (Class B) | 150 | 150 | 150 | 136 |
| (b) | Unplanned interruptions (Class C) | 67 | 67 | 67 | 52 |
| 2006 | 2005 | 2004 | 2003 | 2002 | |
|---|---|---|---|---|---|
| 18. | Average CAIDI Targets (Next 5 Years) | ||||
| (a) | Planned interruptions (Class B) | 150 | 150 | 150 | 136 |
| (b) | Unplanned interruptions (Class C) | 67 | 67 | 67 | 52 |
| 19. | CAIDI for Total Interruptions by Class |
| Class A - Transpower planned interruptions | | 411 | 501 | - |
| Class B - Horizon planned interruptions | 200 | 167 | 111 | 160 |
| Class C - Horizon unplanned interruptions | 141 | 98 | 87 | 125 |
| Class D - Transpower unplanned interruptions | 3,325 | 63 | 22 | 49 |
| Class E - Horizon generation unplanned interruptions | - | - | - | - |
| Class F - Other generation unplanned interruptions | - | - | - | - |
| Class G - Other line owner unplanned interruptions | 122 | - | - | - |
| Class H - Other line owner planned interruptions | - | - | - | - |
| Class I - Not in A to H | - | - | - | - |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2005, No 127
Gazette.govt.nz —
NZ Gazette 2005, No 127
✨ LLM interpretation of page content
🏭
Energy Delivery Efficiency Performance Measures for Horizon Energy Distribution Limited
(continued from previous page)
🏭 Trade, Customs & Industry17 August 2005
Energy Delivery, Efficiency, Performance Measures, Electricity, Horizon Energy, SAIFI, CAIDI, Interruptions, Targets