β¨ Electricity Reliability Performance Measures
17 JANUARY 2005
NEW ZEALAND GAZETTE, No. 10
231
Requirement 21 (3)
- Total number of interruptions, together with a breakdown of that total according to interruption class.
| Interruption Class | Number of Interruptions | |||
|---|---|---|---|---|
| 2004 | 2003 | 2002 | 2001 | |
| MainPower Planned Shut-Down (Class B) | 212 | 167 | 154 | 94 |
| Unplanned Interruption (Class C) | 82 | 102 | 74 | 191 |
| Trans Power Planned Shut-Down (Class A) | 0 | 3 | 3 | - |
| Unplanned Interruption (Class D) | 1 | 2 | - | - |
| Generation Unplanned Interruption (Class E) | 0 | - | - | - |
| Generation Other Unplanned Interruption (Class F) | 0 | - | - | - |
| Other Other Interruptions (Class G) | 0 | - | - | - |
| Unplanned Interruption (Class G) | 0 | - | - | - |
| Total Interruptions | 295 | 274 | 231 | 285 |
- The total number of faults per 100 circuit kilometres of prescribed voltage electric line.
| Nominal Voltage | Faults per 100 km Total | |||
|---|---|---|---|---|
| 2004 | 2003 | 2002 | 2001 | |
| 33 kV | 4.00 | 0.35 | 1.40 | 1.78 |
| 11 kV | 2.01 | 3.23 | 2.09 | 5.52 |
| TOTAL | 2.18 | 2.97 | 2.03 | 5.24 |
- The total number of faults per 100 circuit kilometres of Underground prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.
| Nominal Voltage | Faults per 100 km Underground | |||
|---|---|---|---|---|
| 2004 | 2003 | 2002 | 2001 | |
| 33 kV | - | - | - | - |
| 11 kV | 1.45 | - | 3.15 | 5.30 |
| TOTAL | 1.42 | - | 3.08 | 5.19 |
- The total number of faults per 100 circuit kilometres of Overhead prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.
| Nominal Voltage | Faults per 100 km Overhead | |||
|---|---|---|---|---|
| 2004 | 2003 | 2002 | 2001 | |
| 33 kV | 4.03 | 0.35 | 1.41 | 1.79 |
| 11 kV | 2.03 | 3.34 | 2.06 | 5.53 |
| TOTAL | 2.19 | 3.06 | 2.01 | 5.24 |
-
The SAIDI for the total of interruptions: 99.64 284.35 213.73 151.96
-
The SAIDI for the total number of interruptions within each interruption class:
| Network or Generation Owner | Classification | Minutes per Connected Customer | |||
|---|---|---|---|---|---|
| 2004 | 2003 | 2002 | 2001 | ||
| MainPower | Planned Shut-Down (Class B) | 48.59 | 60.83 | 108.62 | 60.48 |
| Unplanned Interruption (Class C) | 45.44 | 77.87 | 52.12 | 91.48 | |
| Trans Power | Planned Shut-Down (Class A) | 0.00 | 74.38 | 52.98 | - |
| Unplanned Interruption (Class D) | 6.12 | 71.27 | - | - | |
| Generation | Unplanned Interruption (Class E) | - | - | - | - |
| Generation Other | Unplanned Interruption (Class F) | - | - | - | - |
| Other | Other Interruptions (Class G) | - | - | - | - |
| Unplanned Interruption (Class G) | - | - | - | - |
- The SAIFI for the total number of interruptions: 1.21 2.70 1.45 2.08
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2005, No 10
Gazette.govt.nz —
NZ Gazette 2005, No 10
β¨ LLM interpretation of page content
π
Disclosure of Reliability Performance Measures
(continued from previous page)
π Trade, Customs & IndustryReliability Performance, Interruptions, Electricity, MainPower, TransPower, ECNZ