B. RELIABILITY PERFORMANCE MEASURES (1999 REGULATIONS)
B1. Total number of interruptions, together with a breakdown of that total according to interruption class.
| Interruption Class | Number of Interruptions | |||
|---|---|---|---|---|
| 2003 | 2002 | 2001 | 2000 | |
| ------------------------------------ | ----------------------- | ------- | ------- | ------- |
| MainPower | ||||
| Planned Shut-Down (Class B) | 167 | 154 | 94 | 106 |
| Unplanned Interruption (Class C) | 102 | 74 | 191 | 189 |
| Trans Power | ||||
| Planned Shut-Down (Class A) | 3 | 3 | - | 1 |
| Unplanned Interruption (Class D) | 2 | - | - | 1 |
| Generation | ||||
| Unplanned Interruption (Class E) | - | - | - | - |
| Generation Other | ||||
| Unplanned Interruption (Class F) | - | - | - | - |
| Other | ||||
| Other Interruptions (Class G) | - | - | - | - |
| Unplanned Interruption (Class G) | - | - | - | - |
| Total Interruptions | 274 | 231 | 285 | 297 |
B2. The total number of faults per 100 circuit kilometres of prescribed voltage electric line.
| Nominal Voltage | Faults per 100 km Total | |||
|---|---|---|---|---|
| 2003 | 2002 | 2001 | 2000 | |
| ----------------- | ----------------------- | ------- | ------- | ------- |
| 33 kV | 0.348 | 1.40 | 1.78 | 2.04 |
| 11 kV | 3.23 | 2.09 | 5.52 | 5.92 |
| TOTAL | 2.97 | 2.03 | 5.24 | 5.51 |
B3. The total number of faults per 100 circuit kilometres of Underground prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.
| Nominal Voltage | Faults per 100 km Underground | |||
|---|---|---|---|---|
| 2003 | 2002 | 2001 | 2000 | |
| ----------------- | ----------------------------- | ------- | ------- | ------- |
| 33 kV | - | - | - | - |
| 11 kV | - | 3.15 | 5.30 | 7.89 |
| TOTAL | - | 3.08 | 5.19 | 7.69 |
B4. The total number of faults per 100 circuit kilometres of Overhead prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.
| Nominal Voltage | Faults per 100 km Overhead | |||
|---|---|---|---|---|
| 2003 | 2002 | 2001 | 2000 | |
| ----------------- | -------------------------- | ------- | ------- | ------- |
| 33 kV | 0.35 | 1.41 | 1.79 | 0.75 |
| 11 kV | 3.34 | 2.06 | 5.53 | 5.86 |
| TOTAL | 3.06 | 2.01 | 5.24 | 5.45 |
B5. The SAIDI for the total of interruptions:
| 2003 | 2002 | 2001 | 2000 |
|---|---|---|---|
| 284.35 | 213.73 | 151.96 | 116.94 |
B6. The SAIDI for the total number of interruptions within each interruption class:
| Network or Generation Owner | Classification | Minutes per Connected Customer | |||
|---|---|---|---|---|---|
| 2003 | 2002 | 2001 | 2000 | ||
| ----------------------------- | --------------------------------- | ---------------------------------- | ------- | ------- | ------- |
| MainPower | Planned Shut-Down (Class B) | 60.83 | 108.62 | 60.48 | 22.06 |
| Unplanned Interruption (Class C) | 77.87 | 52.12 | 91.48 | 71.55 | |
| Trans Power | Planned Shut-Down (Class A) | 74.38 | 52.98 | - | 22.27 |
| Unplanned Interruption (Class D) | 71.27 | - | - | 1.06 | |
| Generation | Unplanned Interruption (Class E) | - | - | - | - |
| Generation Other | Unplanned Interruption (Class F) | - | - | - | - |
| Other | Other Interruptions (Class G) | - | - | - | - |
| Unplanned Interruption (Class G) | - | - | - | - |
B7. The SAIFI for the total number of interruptions:
| 2003 | 2002 | 2001 | 2000 |
|---|---|---|---|
| 2.70 | 1.45 | 2.08 | 1.77 |
PUBLISHED BY THE
DEPARTMENT OF INTERNAL AFFAIRS
PRINTED BY WICKLIFFE LIMITED
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2004, No 3
Gazette.govt.nz —
NZ Gazette 2004, No 3
β¨ LLM interpretation of page content
π
MainPower New Zealand Limited Information Disclosure Update
(continued from previous page)
π Trade, Customs & IndustryElectricity, Reliability, Performance Measures, Interruptions, Faults, SAIDI, SAIFI, MainPower, Trans Power