✨ Electricity Performance Measures




REGULATION 21

YEAR ENDED 31 MARCH 2003

Energy Delivery Efficiency Performance Measures

2003 2002 2001 2000
a) Load Factor 59.11 58.62 59.57 61.13
b) Loss Ratio 5.17 5.5 5.47 5.39
c) Capacity Utilisation 29.96 30.3 30.1 28.81

Energy Delivery Efficiency Performance Measures

a) Systems Length (kms)

Voltage 2003 2002 2001 2000
~ 33kV 337 271 271 263
~ 11kV 3145 2325 2311 2273
~ 230/400V 2561 1307 1290 1282
Total 6043 3903 3872 3824

b) Circuit Length (Overhead) (kms)

Voltage 2003 2002 2001 2000
~ 33kV 312 248 247 246
~ 11kV 2692 1941 1937 1932
~ 230/400V 675 480 479 474
Total 3679 2669 2663 2652

c) Circuit Length (Underground) (kms)

Voltage 2003 2002 2001 2000
~ 33kV 25 24 24 17
~ 11kV 453 384 374 347
~ 230/400V 1886 826 81 808
Total 2364 1234 1209 1172

d) Transformer Capacity (kVA)

| Total | 727,931| 557,000| 538,831| 536,485|

e) Maximum Demand (kW)

| Total | 218,070| 168,896| 162,200| 154,587|

f) Total Electricity Supplied (kWh)

| Total | 1,130,299,496 | 819,612,086 | 801,999,537 | 783,161,169 |

g) Total electricity conveyed for each Retailer including losses (kWh)

Retailer 2003 2002 2001 2000
Contact Retailer A 631,593,356 578,215,470 563,985,132 583,355,709
Mercury Retailer B 18,766,889 16,294,788 98,491,123 98,444,884
Meridian Retailer C 96,782,760 84,246,438 74,172,364 66,824,649
Transalta Retailer D - 102,569,770 60,083,396 54,210,978
Trustpower Retailer E 204,046,522 18,104,242 30,331,255 25,441,206
Genesis Retailer F 156,844,938 52,586,265 7,224,965 486,864
Waikato Retailer G - 9,356,797 12,928,576 21,168
Empower Retailer H - 0 887,729 21,168
Phoenix Retailer I - 0 0 11,904
Todd Retailer K 15,083,599 2,349,605 329,522 -
Energy Online Retailer J 47,458,002 3,508,849 - -
Total 1,170,556,066 867,332,224 848,445,966 828,306,626

h) Total customers

Year Total
2003 76,469
2002 58,070
2001 57,331
2000 56,594

Note:
The information from (a) to (e) as disclosed above has been time-weighted to reflect the acquisition of Taupo and Rotorua distribution assets from United Networks. This is calculated by averaging the acquired component of the information in (a) to (e) for the five month period and adding this to data held by the Company for the twelve month period. An example of the time weighting of System Lengths is calculated as follows:

System Lengths Owned by Unison from 1 April to 31 March 03 (A) 4660 km
System Lengths Acquired by from 1 November to 31 March 03 (B) 3366 km
Average System Lengths = A + (B x 365) x 150
Average System Lengths Result (as per (a) above) 6043



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2003, No 122


Gazette.govt.nz PDF NZ Gazette 2003, No 122





✨ LLM interpretation of page content

🏭 Unison Networks Limited Reliability Performance Measures (continued from previous page)

🏭 Trade, Customs & Industry
Reliability Measures, Interruptions, Faults, SAIDI, SAIFI, CAIDI, Electricity Regulation

🏭 Energy Delivery Efficiency Performance Measures for Year Ended 31 March 2003

🏭 Trade, Customs & Industry
Energy Efficiency, Load Factor, Loss Ratio, Capacity Utilisation, Electricity Delivery, Performance Measures

🏭 Energy Delivery Efficiency Performance Measures - Systems Length

🏭 Trade, Customs & Industry
Systems Length, Voltage, Circuit Length, Overhead, Underground, Transformer Capacity, Maximum Demand, Electricity Supplied, Retailers

🏭 Total Electricity Conveyed for Each Retailer

🏭 Trade, Customs & Industry
Electricity Conveyed, Retailers, Contact, Mercury, Meridian, Transalta, Trustpower, Genesis, Waikato, Empower, Phoenix, Todd, Energy Online

🏭 Total Customers

🏭 Trade, Customs & Industry
Total Customers, Yearly Data

🏭 Time-Weighted Calculation for Acquired Distribution Assets

🏭 Trade, Customs & Industry
Time-Weighted Calculation, Acquired Assets, System Lengths, Taupo, Rotorua, United Networks