7 SEPTEMBER

NEW ZEALAND GAZETTE

3159

Class C

SAIDI SAIFI CAIDI
Target 31/03/02 66 1.56 42.30
31/03/2002 Avg forecast 69 1.50 46.00
31/03/2003 Avg forecast 67 1.46 46.00
31/03/2004 Avg forecast 65 1.50 43.30
31/03/2005 Avg forecast 64 1.46 43.84
31/03/2006 Avg forecast 64 1.46 43.84

B. RELIABILITY PERFORMANCE MEASURES (1999 REGULATIONS)

B1. Total number of interruptions, together with a breakdown of that total according to interruption class.

Interruption Class Number of Interruptions
2001
MainPower
Planned Shut-Down (Class B) 94
Unplanned Interruption (Class C) 191
Trans Power
Planned Shut-Down (Class A) -
Unplanned Interruption (Class D) -
Generation
Unplanned Interruption (Class E) -
Generation Other
Unplanned Interruption (Class F) -
Other
Other Interruptions (Class G) -
Total Unplanned Interruptions 285

B2. The total number of faults per 100 circuit kilometres of prescribed voltage electric line.

5.63 faults
5.51 faults
4.27 faults
16.62 Faults

B3. The total number of faults per 100 circuit kilometres of underground prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.

Nominal Voltage Faults per 100-km
2001
33 kV -
11 kV 5.30
TOTAL 5.19

B4. The total number of faults per 100 circuit kilometres of overhead prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.

Nominal Voltage Faults per 100-km
2001
33 kV 1.79
11 kV 5.53
TOTAL 5.65

B5. The SAIDI for the total of interruptions:

2001 151.96
2000 116.94
1999 204.71
1998 225.05

B6. The SAIDI for the total number of interruptions within each interruption class:

Network or Generation Owner Classification Minutes per Connected Customer
2001
MainPower Planned Shut-Down (Class B) 60.48
Unplanned Interruption (Class C) 91.48
Trans Power Planned Shut-Down (Class A) -
Unplanned Interruption (Class D) -
Generation Unplanned Interruption (Class E) -
Generation Other Unplanned Interruption (Class F) -
Other Other Interruptions (Class G) -
Unplanned Interruption (Class G) -


Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2001, No 120


Gazette.govt.nz PDF NZ Gazette 2001, No 120