β¨ Electricity Network Performance Metrics
4030 NEW ZEALAND GAZETTE No. 169
(6) The total number of faults per 100 cct km of underground prescribed voltage electric lines
| 1999 | 1998 | 1997 | 1996 | |
|---|---|---|---|---|
| - 50kV | Nil | Nil | Nil | Nil |
| - 11kV | 9.28 | 5.15 | 10.31 | 9.38 |
| - Total | 9.28 | 5.15 | 10.31 | 9.38 |
(7) The total number of faults per 100 cct km of overhead prescribed voltage electric lines
| 1999 | 1998 | 1997 | 1996 | |
|---|---|---|---|---|
| - 50kV | 5.04 | 5.81 | 7.39 | 6.23 |
| - 11kV | 5.95 | 5.59 | 8.12 | 7.01 |
| - Total | 5.66 | 5.62 | 8.04 | 6.92 |
(8) The SAIDI for total of interruptions
| Year | SAIDI |
|---|---|
| 1999 | 404.01 |
| 1998 | 518.77 |
| 1997 | 714.82 |
| 1996 | 569.49 |
(9) The SAIDI targets for the following financial year
(a) Class B ... 148
(b) Class C ... 228
(10) The average SAIDI targets for the following financial year and subsequent 4 financial years
(a) Class B ... 121
(b) Class C ... 206
(11) The SAIDI for total of interruptions within each interruption class
| Class | 1999 | 1998 | 1997 | 1996 |
|---|---|---|---|---|
| Class A | 0 | 0 | 0 | 0 |
| Class B | 164.46 | 235.95 | 180.25 | 167.83 |
| Class C | 239.55 | 253.16 | 532.49 | 401.66 |
| Class D | Nil | 29.66 | 2.08 | Nil |
| Class E | 0 | 0 | 0 | 0 |
| Class F | 0 | 0 | 0 | 0 |
| Class G | 0 | 0 | 0 | 0 |
(12) The SAIFI for total of interruptions
| Year | SAIFI |
|---|---|
| 1999 | 4.16 |
| 1998 | 8.71 |
| 1997 | 5.61 |
| 1996 | 4.98 |
(13) The SAIFI targets for the following financial year
(a) Class B ... 1.20
(b) Class C ... 2.68
(14) The average SAIFI targets for the following financial year and subsequent 4 financial years
(a) Class B ... 0.98
(b) Class C ... 2.43
(15) The SAIFI for total of interruptions within each interruption class
| Class | 1999 | 1998 | 1997 | 1996 |
|---|---|---|---|---|
| Class A | 0 | 0 | 0 | 0 |
| Class B | 1.33 | 2.44 | 1.25 | 1.15 |
| Class C | 2.83 | 4.12 | 4.32 | 3.83 |
| Class D | Nil | 2.16 | 0.04 | Nil |
| Class E | 0 | 0 | 0 | 0 |
| Class F | 0 | 0 | 0 | 0 |
| Class G | 0 | 0 | 0 | 0 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1999, No 169
NZLII —
NZ Gazette 1999, No 169
β¨ LLM interpretation of page content
π°
Financial and Efficiency Performance Measures for Eastland Network Limited
(continued from previous page)
π° Finance & RevenueFinancial performance, Efficiency measures, Electricity, Eastland Network Limited, Disclosure