β¨ Electricity Performance Statistics
3124
NEW ZEALAND GAZETTE
No. 129
20.7 Total Number Of Faults Per 100km Of Prescribed Voltage Overhead Line
| Nominal Voltage | 1999 Powerco Number of Faults/100km | 1998 Powerco Number of Faults/100km | 1997 Powerco Number of Faults/100km | 1996 Powerco Number of Faults/100km | 1995 Taranaki Energy Number of Faults/100km | 1995 Powerco Number of Faults/100km |
|---|---|---|---|---|---|---|
| 110kV | ||||||
| 33kV | 0.00 | 5.77 | 5.65 | 5.47 | 12.77 | 10.82 |
| 22kV | 9.72 | 7.07 | 8.84 | 15.80 | 0.00 | 79.30 |
| 11kV | 10.12 | 11.99 | 10.84 | 15.13 | 28.64 | 12.11 |
| 6.6kV | 0.60 | 1.70 | 7.38 | 8.98 | 16.74 | 4.13 |
| Total | 8.57 | 9.95 | 9.81 | 13.21 | 22.44 | 13.24 |
20.8 SAIDI
| Interruption Class | 1999 Powerco SAIDI | 1998 Powerco SAIDI | 1997 Powerco SAIDI | 1996 Powerco SAIDI | 1995 Taranaki Energy SAIDI | 1995 Powerco SAIDI |
|---|---|---|---|---|---|---|
| Class A - Transpower Planned | 10.46 | 13.11 | 22.81 | 32.16 | 0.00 | 68.79 |
| Class B - Distributor Planned | 23.79 | 34.95 | 74.91 | 65.36 | 101.17 | 65.62 |
| Class C - Distributor Unplanned | 100.80 | 106.29 | 94.50 | 76.29 | 104.52 | 209.28 |
| Class D - Transpower Unplanned | 3.22 | 23.50 | 4.98 | 15.28 | 5.45 | 23.07 |
| Class E - ECNZ Unplanned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Class F - Other Generator Unplanned | 0.00 | 0.00 | 0.16 | 0.00 | 0.00 | 0.00 |
| Class G - Other (Not in A to F) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Class H - Other Owner | 0.00 | |||||
| Class I - Other Owner (Not in A - I) | 0.00 | |||||
| Total | 138.27 | 177.86 | 197.36 | 189.09 | 211.14 | 366.76 |
20.9 SAIDI - Targeted for the Following Financial Year
| Interruption Class | 1999 Powerco SAIDI |
|---|---|
| Class B - Distributor Planned | 23.26 |
| Class C - Distributor Unplanned | 98.77 |
20.10 - 21.11 SAIDI
Targeted for the Following Financial Year and Subsequent 4 Financial Years
| Interruption Class | 1999 Powerco SAIDI |
|---|---|
| Class B - Distributor Planned | 23.26 |
| Class C - Distributor Unplanned | 98.77 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1999, No 129
NZLII —
NZ Gazette 1999, No 129
β¨ LLM interpretation of page content
π
Disclosure of Performance Measures for Powerco Limited
(continued from previous page)
π Trade, Customs & IndustryElectricity, Information Disclosure, Performance Measures, Faults, Voltage Lines, Powerco Limited