β¨ Reliability Performance Measures
NEW ZEALAND GAZETTE
No. 149
Reliability Performance Measures for the Year Ended 31 March 1997
| Consumer Connections | Line 33kV | Line 11kV | Line 6.6kV | Cable 33kV | Cable 11kV | Cable 6.6kV | Total | Density Con/km | |
|---|---|---|---|---|---|---|---|---|---|
| At start of period | 49,837 | 149.9 | 236.5 | 488.1 | 75.2 | 20.4 | 229.5 | 1,200 | 41.5 |
| At end of period | 49,891 | 149.9 | 236.6 | 488.9 | 75.2 | 20.7 | 230.6 | 1,202 | 41.5 |
| Average | 49,864 | 149.9 | 236.5 | 488.5 | 75.2 | 20.5 | 230.0 | 1,201 | 41.5 |
| Totals | 875.0 | 325.8 |
Reliability Measure
| Reliability Measure | SAIDI | SAIFI | CAIDI | No of Interruptions | Class |
|---|---|---|---|---|---|
| Cons Mins Mins/Cons | Cons Int Int/Cons | Mins/Int | |||
| Distributor Planned | 103.921 2.08 | 2.399 0.05 | 43.30 | 14 | B |
| Distributor Unplanned | 2,802.324 56.20 | 47.642 0.96 | 58.80 | 115 | C |
| Subtotal | 2,906,245 58.28 | 50.041 1.00 | 58.10 | 129 | |
| Transpower Planned | - | - | - | - | A |
| Transpower Unplanned | - | - | - | - | D |
| Subtotal | - | - | - | - | |
| ECNZ Planned | - | - | - | - | G |
| ECNZ Unplanned | - | - | - | - | E |
| Subtotal | - | - | - | - | |
| Other Gen Planned | - | - | - | - | |
| Other Gen Unplanned | - | - | - | - | F |
| Other Than Above | - | - | - | - | |
| Subtotal | - | - | - | - | |
| TOTAL | 2,906,245 58.28 | 50.041 1.00 | 58.10 | 129 |
Faults by Voltage
| Faults by Voltage | OH Faults | OH Length km | OH per 100 km | Cable Faults | UG Length km | UG per 100 km |
|---|---|---|---|---|---|---|
| 33kV | 4 | 149.9 | 2.7 | 3 | 75.2 | 4.0 |
| 11kV | 43 | 236.5 | 18.2 | 1 | 20.5 | 4.9 |
| 6.6kV | 48 | 488.5 | 9.8 | 12 | 230.0 | 5.2 |
| TOTAL | 95 | 875.0 | 10.9 | 16 | 325.8 | 4.9 |
| Total Lines and Cables | Total Faults | Total Length in km | Faults per 100 km |
|---|---|---|---|
| 111 | 1,201 | 9.2 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1998, No 149
NZLII —
NZ Gazette 1998, No 149
β¨ LLM interpretation of page content
π
Reliability Performance Measures for Electricity Sector
(continued from previous page)
π Trade, Customs & IndustryReliability Measures, Performance, Electricity Sector, Consumer Connections, Faults