✨ Electricity Reliability Statistics




NEW ZEALAND GAZETTE

No. 84

THE POWER COMPANY LIMITED

RELIABILITY PERFORMANCE MEASURES

(LINE BUSINESS)

PURSUANT TO REGULATION 16
ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1994

11.0 RELIABILITY STATISTICS REQUIRED FOR THE DISCLOSURE REGULATIONS

APRIL 1994 - MARCH 1995, APRIL 1995 - MARCH 1996, APRIL 1996 - MARCH 1997

Connected Customers Line 66kV Line 33kV Line 11kV Line 400V Cable 33kV Cable 11kV Cable 6.6kV Cable 400V Total Density Cust/km
1994/95 Average 34182 239 467 6392 1013 0.75 39 0.59 95 8247 4.14
1995/96 Average 32941 239 468 6397 1012 0.75 41 0.59 96 8254 3.99
1996/97 Average 30589 246 462 6401 1013 0.75 42 0.59 98 8263 3.70
CLASS B C Subtotal A D Subtotal E Subtotal F Subtotal G TOTAL
Interruptions 287 336 623 0 1 1 0 0 0 0 0 624
SAIDI 35.6 125.4 161 0 0.4 0.4 0 0 0 0 0 161.4
SAIFI 0.372 2.099 2.471 0 0.15 0.15 0 0 0 0 0 2.621
CAIDI 96 60 65 0 3 3 0 0 0 0 0 62

| Interruptions | 384 | 428 | 812 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 812 |
| SAIDI | 65.6 | 300.6 | 366.2 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 366.2 |
| SAIFI | 0.52 | 3.475 | 3.995 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 3.995 |
| CAIDI | 176 | 86 | 95 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 95 |

| Interruptions | 439 | 483 | 922 | 0 | 3 | 3 | 0 | 0 | 0 | 0 | 0 | 925 |
| SAIDI | 65.7 | 418.4 | 484.1 | 0 | 8.2 | 8.2 | 0 | 0 | 0 | 0 | 0 | 492.3 |
| SAIFI | 0.532 | 5.081 | 5.613 | 0 | 1.002| 1.002 | 0 | 0 | 0 | 0 | 0 | 6.615 |
| CAIDI | 123.4 | 82.4 | 86.3 | 0 | 8.18| 8.18 | 0 | 0 | 0 | 0 | 0 | 74.4 |

Unplanned Faults by Voltage

66kV 33kV 11kV 6.6kV Total Lines and Cables
1994/95 OH per 100km 2.1 1.3 5 0 4.6
1994/95 UG per 100km 0 0 23.2 0 22.4
Total per 100km 2.1 1.3 5.1 0 4.1

| 1995/96 OH per 100km | 1.7 | 2.6 | 12.1 | 0 | 11.1 |
| 1995/96 UG per 100km | 0 | 0 | 14.3 | 0 | 14.1 |
| Total per 100km | 1.7 | 2.6 | 12.1 | 0 | 5.2 |

| 1996/97 OH per 100km | 0.4 | 2.1 | 13.1 | 0 | 11.9 |
| 1996/97 UG per 100km | 0 | 0 | 26.9 | 0 | 25.8 |
| Total per 100km | 0.4 | 2.1 | 13.17 | 0 | 12.13 |



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


NZLII PDF NZ Gazette 1997, No 84





✨ LLM interpretation of page content

🏭 Energy Efficiency Performance Measures and Statistics by The Power Company Limited (continued from previous page)

🏭 Trade, Customs & Industry
Electricity, Energy Efficiency, Performance Measures, Statistics, Transmission System, Line Business