Electricity Transmission Statistics




4574

NEW ZEALAND GAZETTE

No. 173

The Electricity (Information Disclosure) Regulations 1994

(For 12 Months ending 30 June 1996, 30 June 1995, and 30 June 1994)

Part III

Energy Delivery Efficiency Performance

Measures And Statistics

(Disclosure Under Regulation 15)

  1. Energy delivery efficiency performance measures

(a) Load factor ........................................... 67.26% 68.05% **68.96%

Percentage of electrical energy entering the transmission system over maximum demand times hours per year

(b) Loss ratio ........................................... 5.69% 6.16% 6.09%

Transmission losses over energy entering the system

(c) Capacity utilisation ................................. 70.99% 70.53% 66.91%

Maximum demand over total transformer capacity

  1. Statistics

(a) System length, broken down by voltage

Total .................................................. 17,739 km 17,626 km 17,629 km

350 kV (HVDC) .......................................... 611 km 611 km 611 km

270 kV (HVDC) .......................................... 611 km 611 km 611 km

0 kV (HVDC earth electrode) ............................ 31 km 31 km 31 km

220 kV (HVAC) .......................................... 8,361 km 8,364 km 8,367 km

110 kV (HVAC) .......................................... 6,384 km 6,333 km 6,372 km

66/50/33/11 kV ....................................... 1,741 km 1,676 km 1,637 km

(b) Circuit length of overhead electric lines, broken down by voltage:

Total .................................................. 17,659 km 17,546 km 17,549 km

350 kV (HVDC) .......................................... 571 km 571 km 571 km

270 kV (HVDC) .......................................... 571 km 571 km 571 km

0 kV (HVDC earth electrode) ............................ 31 km 31 km 31 km

220 kV (HVAC) .......................................... 8,361 km 8,364 km 8,367 km

110 kV (HVAC) .......................................... 6,384 km 6,333 km 6,372 km

66/50/33/11 kV ....................................... 1,741 km 1,676 km 1,637 km

NB: HVDC link submarine power cables measure approximately 80km.

Broken down by voltage:

350 kV (HVDC) .......................................... 40 km 40 km 40 km

270 kV (HVDC) .......................................... 40 km 40 km 40 km

(c) Total circuit length of underground electric lines ........................................... 0 km 0 km 0 km

(d) Transformer capacity (kilovolt amperes) ........................................... 7.9910⁶ kVA 7.7710⁶ kVA 7.9210⁶ kVA

(e) Maximum demand (kilowatts) ........................................... 5.6710⁶ kW 5.4810⁶ kW 5.3010⁶ kW

(f) Total electricity supplied from the system (kilowatt hours) ........................................... 31.5310⁹kWh 30.6610⁹kWh 30.0810⁹kWh

(g) Total electricity conveyed through the system (kilowatt hours) ........................................... 33.4310⁹kWh 32.6710⁹kWh 32.0310⁹kWh

(h) Total customers .................................... 49 49 49

  • to 2 decimal places only, higher accuracy used in calculations

** This figure has been changed from that published in the 1994/95 gazetted information (was 68.95).



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1996, No 173


NZLII PDF NZ Gazette 1996, No 173





✨ LLM interpretation of page content

🏭 Optimised Deprival Valuation Report for Trans Power New Zealand Limited (continued from previous page)

🏭 Trade, Customs & Industry
Valuation, Fixed Assets, Financial Reporting, ODV, Transpower

🏭 Energy Delivery Efficiency Performance Measures and Statistics

🏭 Trade, Customs & Industry
Electricity, Transmission, Efficiency, Statistics, Load Factor, Loss Ratio, Capacity Utilisation, System Length, Circuit Length, Transformer Capacity, Maximum Demand, Electricity Supply