✨ Electricity Reliability Performance




2470
NEW ZEALAND GAZETTE
No. 86

CENTRAL ELECTRIC LIMITED

RELIABILITY PERFORMANCE MEASURES

PURSUANT TO REGULATION 16 OF THE ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1994


REG 16 - PART IV

Reliability Performance Measures

Sect 1
Total Number of Interruptions 313

Interruptions by Class
Class
A 0
B 161
C 149
D 3
E 0
F 0
G 0

Sect 2
Total Faults 149
Line Length 1617.25
Faults per 100km 9.21

Sect 3
Underground Cables
Nominal Voltage # Faults Average Length (km) Faults per 100km
33kV 0 2.38 0.00
11kV 9 43.33 20.77
6.6kV 0 0 0.00
TOTAL 9 45.71 19.69

Sect 4
Overhead Lines
Nominal Voltage # Faults Average Length (km) Faults per 100km
33kV 11 413.46 2.66
11kV 121 1201.53 10.07
6.6kV 8 29.26 27.34
TOTAL 140 1644.25 8.51

Sect 5 SAIDI Total Interruptions (all Classes)
Cust-Mins 4936447
Customers 17280
SAIDI 285.67



Next Page →