β¨ Electricity Reliability Performance
2470
NEW ZEALAND GAZETTE
No. 86
CENTRAL ELECTRIC LIMITED
RELIABILITY PERFORMANCE MEASURES
PURSUANT TO REGULATION 16 OF THE ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1994
REG 16 - PART IV
Reliability Performance Measures
Sect 1
Total Number of Interruptions 313
Interruptions by Class
Class
A 0
B 161
C 149
D 3
E 0
F 0
G 0
Sect 2
Total Faults 149
Line Length 1617.25
Faults per 100km 9.21
Sect 3
Underground Cables
Nominal Voltage # Faults Average Length (km) Faults per 100km
33kV 0 2.38 0.00
11kV 9 43.33 20.77
6.6kV 0 0 0.00
TOTAL 9 45.71 19.69
Sect 4
Overhead Lines
Nominal Voltage # Faults Average Length (km) Faults per 100km
33kV 11 413.46 2.66
11kV 121 1201.53 10.07
6.6kV 8 29.26 27.34
TOTAL 140 1644.25 8.51
Sect 5 SAIDI Total Interruptions (all Classes)
Cust-Mins 4936447
Customers 17280
SAIDI 285.67
Next Page →