β¨ Electricity Reliability Statistics
NEW ZEALAND GAZETTE
15 AUGUST
2185
DUNEDIN ELECTRICITY LTD
RELIABILITY PERFORMANCE MEASURES
PURSUANT TO REGULATION 16 ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1994
Reliability Statistics Required for the Disclosure Regulations April 1994 - March 1995
| Connected Customers | Line 33kV | Line 11kV | Line 6.6kV | Cable 33kV | Cable 11kV | Cable 6.6kV | Total | Density Cust/km |
|---|---|---|---|---|---|---|---|---|
| At start of period | 49,050 | 149.9 | 233.9 | 482.5 | 75.2 | 19.7 | 226.5 | 1,188 |
| At end of period | 49,730 | 149.9 | 235.8 | 485.0 | 75.2 | 20.2 | 228.7 | 1,195 |
| Average | 49,390 | 149.9 | 234.8 | 483.8 | 75.2 | 19.9 | 227.6 | 1,191 |
| Average line/cable | 149.9 | 234.8 | 868.5 | 19.9 | 322.8 | 1,191 |
Interruptions Summary
| SAIDI Cust Mins | SAIFI Mins/Cust | CAIDI Cust Int | Int/Cust | Mins/Int | No Interruptions | Class | |
|---|---|---|---|---|---|---|---|
| Disclosure Regulations | |||||||
| Distributor Planned | 203,767 | 4.13 | 2,925 | 0.06 | 69.7 | 27 | B |
| Distributor Unplanned | 1,119,964 | 22.68 | 32,753 | 0.66 | 34.2 | 95 | C |
| Subtotal | 1,323,731 | 26.80 | 35,678 | 0.72 | 37.1 | 122 | |
| Trans Power Planned | - | - | - | - | - | - | A |
| Trans Power Unplanned | 531,031 | 10.75 | 38,436 | 0.78 | 13.8 | 3 | D |
| Subtotal | 531,031 | 10.75 | 38,436 | 0.78 | 13.8 | 3 | |
| ECNZ Planned | - | - | - | - | - | - | E |
| ECNZ Unplanned | - | - | - | - | - | - | |
| Subtotal | - | - | - | - | - | - | |
| Other Gen Planned | - | - | - | - | - | - | F |
| Other Gen Unplanned | - | - | - | - | - | - | |
| Other Than Above | - | - | - | - | - | - | G |
| Subtotal | - | - | - | - | - | - | |
| TOTAL | 1,854,762 | 37.55 | 74,114 | 1.50 | 25.0 | 125 |
Unplanned Faults by Voltage
| Voltage | Lines Faults | OH Length km | OH per 100 km | Cables Faults | UG Length km | UG per 100 km |
|---|---|---|---|---|---|---|
| 33kV | 7 | 149.9 | 4.7 | 1 | 75.2 | 1.3 |
| 11kV | 33 | 234.8 | 14.1 | 2 | 19.9 | 10.0 |
| 6.6kV | 38 | 483.8 | 7.9 | 6 | 227.6 | 2.6 |
| TOTAL | 78 | 868.5 | 9.0 | 9 | 322.8 | 2.8 |
| Total Faults | Total Length in km | No Faults per 100 km | |
|---|---|---|---|
| Total Lines and Cables | 87 | 1,191.2 | 7.3 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1995, No 80
NZLII —
NZ Gazette 1995, No 80
β¨ LLM interpretation of page content
π
Dunedin Electricity Ltd Reliability Performance Measures and Statistics
(continued from previous page)
π Trade, Customs & IndustryElectricity, Reliability, Performance Measures, Statistics, Dunedin Electricity Ltd