TABLE XII.—PERMISSIBLE NUMBER OF CABLES IN CONDUITS, AND CAPACITY OF CONDUITS FOR THE DRAWING-IN OF CABLES.
| Size of Conduit. | ⅝ in. | ¾ in. | 1 in. | 1¼ in. | 1½ in. | 2 in. | 2½ in. |
|---|---|---|---|---|---|---|---|
| Internal Diameter of Conduit (approximate). | 0·498 in. | 0·606 in. | 0·856 in. | 1·106 in. | 1·34 in. | 1·816 in. | 2·316 in. |
| Number and Diameter (Inches) of Wires comprising Conductor. | Nominal Area of Conductor. | Approximate Over-all Diameter of Cable. | Maximum Permissible Number of Cables. | ||||
| 1. | 2. | 3. | 4. | 5. | 6. | 7. | 8. |
| 1/·044 | 0·0015 | 0·173 | 5 | 8 | 11 | — | — |
| 3/·029 | 0·002 | 0·195 | 4 | 6 | 10 | — | — |
| 3/·036 | 0·003 | 0·215 | 3 | 5 | 8 | — | — |
| 7/·029 | 0·0045 | 0·226 | 2 | 4 | 6 | 9 | — |
| 7/·036 | 0·007 | 0·259 | — | 3 | 5 | 8 | — |
| 7/·044 | 0·01 | 0·287 | — | 2 | 4 | 7 | — |
| 7/·052 | 0·0145 | 0·317 | — | — | 3 | 5 | 7 |
| 7/·064 | 0·0225 | 0·359 | — | — | 2 | 4 | 7 |
| 19/·044 | 0·03 | 0·393 | — | — | — | 3 | 5 |
| 19/·052 | 0·04 | 0·441 | — | — | — | 2 | 4 |
| 19/·064 | 0·06 | 0·513 | — | — | — | — | 3 |
| 19/·072 | 0·075 | 0·596 | — | — | — | — | — |
| 19/·083 | 0·1 | 0·663 | — | — | — | — | — |
| 37/·064 | 0·12 | 0·702 | — | — | — | — | — |
| 37/·072 | 0·15 | 0·768 | — | — | — | — | — |
(i) The table applies to 250-volt, vulcanized-rubber, braided cables in accordance with British Standard Specification No. 7, and to screwed conduits which comply with British Standard Specification No. 31.
(ii) The grouping in one tube of more than two of the larger cables is not recommended, and where it is done the current rating given in Tables IV, V, and VI hereof should be reduced to ensure that the cables are not overheated.
(iii) It shall be possible to withdraw any conductor and draw in another of equal size in its place without injury (see Regulation 46–11).
(iv) Where wires of different sizes are installed in the same conduit their outside diameter when bunched shall not exceed the diameter of the number of wires permitted in this table.
TABLE XIII.—APPROXIMATE FUSING CURRENTS OF COPPER WIRES IN FREE AIR.
| Size. | Diameter of Wire. | Fusing Current. | Maximum Safe-working Current. |
|---|---|---|---|
| 1. | 2. | 3. | 4. |
| S.W.G. | In. | Amps. | Amps. |
| 36 | 0·0076 | 6·8 | 3·4 |
| 34 | 0·0092 | 8·6 | 4·3 |
| 33 | 0·010 | 9·8 | 4·9 |
| 32 | 0·0108 | 11·0 | 5·5 |
| — | 0·0120 | 12·8 | 6·4 |
| 30 | 0·0124 | 13·5 | 6·8 |
| 28 | 0·0148 | 17 | 8·6 |
| 26 | 0·018 | 22 | 11 |
| 24 | 0·022 | 30 | 15 |
| 22 | 0·028 | 41 | 21 |
| — | 0·029 | 43 | 22 |
| 20 | 0·036 | 62 | 31 |
| 19 | 0·040 | 73 | 37 |
| — | 0·044 | 86 | 43 |
| 18 | 0·048 | 98 | 49 |
| — | 0·052 | 111 | 56 |
| 17 | 0·056 | 125 | 63 |
| 16 | 0·064 | 156 | 78 |
| 15 | 0·072 | 191 | 96 |
| 14 | 0·080 | 229 | 115 |
The table refers to wires in free air and of the following lengths: 2¼ in. to 3½ in. for wires up to 0·018 in. diameter, and not less than 4 in. for larger wires.
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1935, No 65
NZLII —
NZ Gazette 1935, No 65
✨ LLM interpretation of page content
🏗️ Permissible Number of Cables in Conduits and Capacity of Conduits
🏗️ Infrastructure & Public WorksCables, Conduits, Electrical Standards, Capacity, Wires
🏗️ Approximate Fusing Currents of Copper Wires in Free Air
🏗️ Infrastructure & Public WorksCopper Wires, Fusing Currents, Electrical Standards, Safe-working Current