✨ Electrical Standards Tables
SEPT. 6.] THE NEW ZEALAND GAZETTE. 2569
TABLE IX.—INSULATION RESISTANCE OF CABLES.
| Number and Diameter (Inches) of Wires comprising Conductor. | Nominal Area. | Minimum Insulation Resistance, Megohms for a Mile Length at 60° F. | ||
|---|---|---|---|---|
| Rubber-insulated Cables. | Paper-insulated Cables. | |||
| 600-megohm Grade.* | 2,500-megohm Grade.*† | |||
| 1. | 2. | 3. | 4. | 5. |
| 1/·036 | Sq. in. | Megohms. | Megohms. | Megohms. |
| 1/·044 | 0·001 | 2,000 | 5,000 | 140 |
| 3/·029 | 0·0015 | 2,000 | 5,000 | 140 |
| 0·002 | 1,250 | 4,500 | 140 | |
| 3/·036 | 0·003 | 1,250 | 4,500 | 140 |
| 1/·064 | 0·003 | 2,000 | 5,000 | 140 |
| 7/·029 | 0·0045 | 1,250 | 4,500 | 140 |
| 7/·036 | 0·007 | 900 | 4,000 | 140 |
| 7/·044 | 0·01 | 900 | 4,000 | 140 |
| 7/·052 | 0·0145 | 900 | 4,000 | 140 |
| 7/·064 | 0·0225 | 900 | 3,500 | 130 |
| 19/·044· | 0·03 | 750 | 3,500 | 125 |
| 19/·052 | 0·04 | 750 | 3,000 | 115 |
| 19/·064 | 0·06 | 750 | 3,000 | 100 |
| 19/·072 | 0·075 | 600 | 3,000 | 85 |
| 19/·083 | 0·1 | 600 | 3,000 | 80 |
| 37/·064 | 0·12 | 600 | 3,000 | 75 |
| 37/·072 | 0·15 | 600 | 3,000 | 60 |
| 37/·083 | 0·2 | 600 | 2,500 | 55 |
| 37/·093 | 0·25 | 600 | 2,500 | 50 |
| 37/·103 | 0·3 | 600 | 2,500 | 50 |
| 61/·093 | 0·4 | 600 | 2,500 | 50 |
| 61/·103 | 0·5 | 600 | 2,500 | 45 |
| 91/·093 | 0·6 | 600 | 2,500 | 40 |
| 91/·103 | 0·75 | 600 | 2,500 | 40 |
| 127/·093 | 0·85 | 600 | 2,500 | 35 |
| 127/·103 | 1·0 | 600 | 2,500 | 35 |
- For (a) Direct-current systems for pressures not varying from earth potential by more than 250 volts; (b) three-phase systems, with centre point earthed, for pressures not more than 500 volts between phases.
† For pressures not varying from earth potential by more than 650 volts.
TABLE X.—TEST PRESSURES FOR FLEXIBLE CORDS.
| Kind. | Insulating Material. | Test Pressure and Frequency. | Nature of Test.* |
|---|---|---|---|
| 1. | 2. | 3. | 4. |
| High insulation | (a) Pure rubber | } 1,500 volts | Between conductors in |
| (b) Pure and/or vulcanized-rubber | dry state. | ||
| (c) Homogeneous insulation | } at 25–100 | ||
| Medium insulation | (a) Pure rubber | 1,000 volts | |
| (b) Homogeneous insulation | 1,500 volts |
- Where a flexible cord has a covering purporting to be waterproof it shall be tested after twenty-four hours immersion in water.
TABLE XI.—INSULATION RESISTANCE OF FLEXIBLE CORDS HAVING VULCANIZED-RUBBER INSULATION.
| Number and Diameter of Wires comprising Conductor. | Nominal Area. | Minimum Insulation Resistance, Megohms for a Mile Length at 60° F. | ||
|---|---|---|---|---|
| 0·0076-in.-diameter Wires. | 0·012-in.-diameter Wires. | High Insulation. | Medium Insulation. | |
| 1. | 2. | 3. | 4. | 5. |
| Sq. in. | Megohms. | Megohms. | ||
| 14 | — | 0·0006 | 1,250 | 300 |
| 23 | 11 | 0·001 | 1,250 | 300 |
| 40 | 16 | 0·0017 | 1,250 | 300 |
| 70 | 28 | 0·003 | 1,250 | 300 |
| 110 | 44 | 0·0048 | 1,250 | 300 |
| 162 | 65 | 0·007 | 900 | 300 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1935, No 65
NZLII —
NZ Gazette 1935, No 65
✨ LLM interpretation of page content
🏗️
Insulation Resistance of Cables
(continued from previous page)
🏗️ Infrastructure & Public WorksInsulation Resistance, Cables, Rubber-insulated, Paper-insulated, Electrical Standards
🏗️ Test Pressures for Flexible Cords
🏗️ Infrastructure & Public WorksTest Pressures, Flexible Cords, Insulating Material, Electrical Standards
🏗️ Insulation Resistance of Flexible Cords with Vulcanized-Rubber Insulation