Electrical Standards Tables




SEPT. 6.] THE NEW ZEALAND GAZETTE. 2569

TABLE IX.—INSULATION RESISTANCE OF CABLES.

Number and Diameter (Inches) of Wires comprising Conductor. Nominal Area. Minimum Insulation Resistance, Megohms for a Mile Length at 60° F.
Rubber-insulated Cables. Paper-insulated Cables.
600-megohm Grade.* 2,500-megohm Grade.*†
1. 2. 3. 4. 5.
1/·036 Sq. in. Megohms. Megohms. Megohms.
1/·044 0·001 2,000 5,000 140
3/·029 0·0015 2,000 5,000 140
0·002 1,250 4,500 140
3/·036 0·003 1,250 4,500 140
1/·064 0·003 2,000 5,000 140
7/·029 0·0045 1,250 4,500 140
7/·036 0·007 900 4,000 140
7/·044 0·01 900 4,000 140
7/·052 0·0145 900 4,000 140
7/·064 0·0225 900 3,500 130
19/·044· 0·03 750 3,500 125
19/·052 0·04 750 3,000 115
19/·064 0·06 750 3,000 100
19/·072 0·075 600 3,000 85
19/·083 0·1 600 3,000 80
37/·064 0·12 600 3,000 75
37/·072 0·15 600 3,000 60
37/·083 0·2 600 2,500 55
37/·093 0·25 600 2,500 50
37/·103 0·3 600 2,500 50
61/·093 0·4 600 2,500 50
61/·103 0·5 600 2,500 45
91/·093 0·6 600 2,500 40
91/·103 0·75 600 2,500 40
127/·093 0·85 600 2,500 35
127/·103 1·0 600 2,500 35
  • For (a) Direct-current systems for pressures not varying from earth potential by more than 250 volts; (b) three-phase systems, with centre point earthed, for pressures not more than 500 volts between phases.

† For pressures not varying from earth potential by more than 650 volts.

TABLE X.—TEST PRESSURES FOR FLEXIBLE CORDS.

Kind. Insulating Material. Test Pressure and Frequency. Nature of Test.*
1. 2. 3. 4.
High insulation (a) Pure rubber } 1,500 volts Between conductors in
(b) Pure and/or vulcanized-rubber dry state.
(c) Homogeneous insulation } at 25–100
Medium insulation (a) Pure rubber 1,000 volts
(b) Homogeneous insulation 1,500 volts
  • Where a flexible cord has a covering purporting to be waterproof it shall be tested after twenty-four hours immersion in water.

TABLE XI.—INSULATION RESISTANCE OF FLEXIBLE CORDS HAVING VULCANIZED-RUBBER INSULATION.

Number and Diameter of Wires comprising Conductor. Nominal Area. Minimum Insulation Resistance, Megohms for a Mile Length at 60° F.
0·0076-in.-diameter Wires. 0·012-in.-diameter Wires. High Insulation. Medium Insulation.
1. 2. 3. 4. 5.
Sq. in. Megohms. Megohms.
14 0·0006 1,250 300
23 11 0·001 1,250 300
40 16 0·0017 1,250 300
70 28 0·003 1,250 300
110 44 0·0048 1,250 300
162 65 0·007 900 300


Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1935, No 65


NZLII PDF NZ Gazette 1935, No 65





✨ LLM interpretation of page content

🏗️ Insulation Resistance of Cables (continued from previous page)

🏗️ Infrastructure & Public Works
Insulation Resistance, Cables, Rubber-insulated, Paper-insulated, Electrical Standards

🏗️ Test Pressures for Flexible Cords

🏗️ Infrastructure & Public Works
Test Pressures, Flexible Cords, Insulating Material, Electrical Standards

🏗️ Insulation Resistance of Flexible Cords with Vulcanized-Rubber Insulation

🏗️ Infrastructure & Public Works
Insulation Resistance, Flexible Cords, Vulcanized-Rubber Insulation, Electrical Standards