Electrical Conductor Standards




SEPT. 6.] THE NEW ZEALAND GAZETTE. 2565

TABLE II.—COMPARISON BETWEEN THE OLD STANDARD SIZES OF CON-
DUCTORS AND THE NEW STANDARD SIZES SET OUT IN B.S.S. No. 7.

New Standard. Old Standard.
Number and Diameter (Inches) of Wires comprising Conductor. New Nominal Area. Number and Gauge or Diameter (Inches) of Wires comprising Conductor. Old Nominal Area.
1. 2. 3. 4.
Sq. in. Sq. in.
1/·036 0·001 1/20 S.W.G. 0·001
1/·044 0·0015
1/18 ” 0·0018
3/·029 0·002 3/22 ” 0·0018
3/·036 0·003 7/25 ” 0·0022
3/20 ” 0·003
1/·064 0·003 7/23 ” 0·0031
1/16 ” 0·0032
7/·029 0·0045 7/22 ” 0·0042
7/·036 0·007 7/21¼ ” 0·0049
7/20 ” 0·007
7/·044 0·01 7/19 ” 0·0086
7/·052 0·0145 7/18 ” 0·0125
7/·064 0·0225 7/17 ” 0·017
19/·044 0·03 7/16 ” 0·022
19/·052 0·04 19/18 ” 0·034
7/14 ” 0·035
19/·064 0·06 19/17 ” 0·046
19/·072 0·075 19/16 ” 0·06
19/15 ” 0·075
19/·083 0·1 19/14 ” 0·094
37/·064 0·12 37/16 ” 0·117
19/13 ” 0·125
37/·072 0·15 37/15 ” 0·15
37/14 ” 0·182
37/·083 0·2 37/·083 in. 0·2
37/·093 0·25 37/·092 ” 0·25
37/·103 0·3 37/·104 ” 0·3
61/·093 0·4 61/·092 ” 0·4
61/·103 0·5 61/·104 ” 0·5
91/·093 0·6 61/·112 ” 0·6
91/·103 0·75 91/·101 ” 0·75
127/·093 0·85
127/·103 1·0 127/·101 ,, 1·0

TABLE III.—FLEXIBLE CABLES. DIMENSIONS AND RESISTANCE OF
CONDUCTORS.

(Standard Annealed Copper.)

Number and Diameter of Wires comprising Conductor. Resistance per 1,000 Yards at 60° F.
Diameter 0·010 in. Diameter 0·012 in. Diameter 0·018 in. Diameter 0·029 in. Nominal Area. Standard. Maximum allowable for Plain Wires. Maximum allowable for Tinned Wires.
1. 2. 3. 4. 5. 6. 7. 8.
Sq. in. Ohms. Ohms. Ohms.
140 97* 0·01 2·29 2·34 2·39
195 60* 0·0145 1·64 1·68 1·71
296 91* 0·0225 1·08 1·11 1·13
266 117* 0·03 0·847 0·864 0·881
368 163* 0·04 0·606 0·618 0·631
557 248* 0·06 0·400 0·408 0·416
705 313 121* 0·075 0·316 0·323 0·329
416 160* 0·1 0·238 0·243 0·247
482 186* 0·12 0·206 0·210 0·214
610 235* 0·15 0·163 0·166 0·169
810 312* 0·2 0·122 0·125 0·127
1,017 392* 0·25 0·0974 0·0993 0·101
481 0·3 0·0794 0·0810 0·0826
646 0·4 0·0591 0·0603 0·0614
792 0·5 0·0482 0·0491 0·0501
  • For trailing-cables and similar purposes.

G



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1935, No 65


NZLII PDF NZ Gazette 1935, No 65





✨ LLM interpretation of page content

🏗️ Comparison of Old and New Standard Sizes of Conductors (continued from previous page)

🏗️ Infrastructure & Public Works
Electrical Conductors, Standards, Dimensions, Resistance, Comparison

🏗️ Flexible Cables: Dimensions and Resistance of Conductors

🏗️ Infrastructure & Public Works
Flexible Cables, Conductors, Dimensions, Resistance, Standards