✨ Electrical Conductor Standards




SEPT. 6.] THE NEW ZEALAND GAZETTE. 2565

TABLE II.—COMPARISON BETWEEN THE OLD STANDARD SIZES OF CON-
DUCTORS AND THE NEW STANDARD SIZES SET OUT IN B.S.S. No. 7.

New Standard. Old Standard.
Number and Diameter (Inches) of Wires comprising Conductor. New Nominal Area. Number and Gauge or Diameter (Inches) of Wires comprising Conductor. Old Nominal Area.
1. 2. 3. 4.
Sq. in. Sq. in.
1/·036 0·001 1/20 S.W.G. 0·001
1/·044 0·0015 — —
— — 1/18 ” 0·0018
3/·029 0·002 3/22 ” 0·0018
— — — —
3/·036 0·003 7/25 ” 0·0022
— — 3/20 ” 0·003
1/·064 0·003 7/23 ” 0·0031
— — 1/16 ” 0·0032
7/·029 0·0045 7/22 ” 0·0042
— — — —
7/·036 0·007 7/21¼ ” 0·0049
— — 7/20 ” 0·007
7/·044 0·01 7/19 ” 0·0086
— — — —
7/·052 0·0145 7/18 ” 0·0125
— — — —
7/·064 0·0225 7/17 ” 0·017
19/·044 0·03 7/16 ” 0·022
— — — —
19/·052 0·04 19/18 ” 0·034
— — 7/14 ” 0·035
19/·064 0·06 19/17 ” 0·046
19/·072 0·075 19/16 ” 0·06
— — 19/15 ” 0·075
19/·083 0·1 19/14 ” 0·094
37/·064 0·12 37/16 ” 0·117
— — 19/13 ” 0·125
37/·072 0·15 37/15 ” 0·15
— — 37/14 ” 0·182
37/·083 0·2 37/·083 in. 0·2
37/·093 0·25 37/·092 ” 0·25
37/·103 0·3 37/·104 ” 0·3
61/·093 0·4 61/·092 ” 0·4
61/·103 0·5 61/·104 ” 0·5
91/·093 0·6 61/·112 ” 0·6
91/·103 0·75 91/·101 ” 0·75
127/·093 0·85 — —
127/·103 1·0 127/·101 ,, 1·0

TABLE III.—FLEXIBLE CABLES. DIMENSIONS AND RESISTANCE OF
CONDUCTORS.

(Standard Annealed Copper.)

Number and Diameter of Wires comprising Conductor. Resistance per 1,000 Yards at 60° F.
Diameter 0·010 in. Diameter 0·012 in. Diameter 0·018 in. Diameter 0·029 in. Nominal Area. Standard. Maximum allowable for Plain Wires. Maximum allowable for Tinned Wires.
1. 2. 3. 4. 5. 6. 7. 8.
Sq. in. Ohms. Ohms. Ohms.
140 97* — — 0·01 2·29 2·34 2·39
195 — 60* — 0·0145 1·64 1·68 1·71
296 — 91* — 0·0225 1·08 1·11 1·13
— 266 117* — 0·03 0·847 0·864 0·881
— 368 163* — 0·04 0·606 0·618 0·631
— 557 248* — 0·06 0·400 0·408 0·416
— 705 313 121* 0·075 0·316 0·323 0·329
— — 416 160* 0·1 0·238 0·243 0·247
— — 482 186* 0·12 0·206 0·210 0·214
— — 610 235* 0·15 0·163 0·166 0·169
— — 810 312* 0·2 0·122 0·125 0·127
— — 1,017 392* 0·25 0·0974 0·0993 0·101
— — — 481 0·3 0·0794 0·0810 0·0826
— — — 646 0·4 0·0591 0·0603 0·0614
— — — 792 0·5 0·0482 0·0491 0·0501
  • For trailing-cables and similar purposes.

G



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa — PDF NZ Gazette 1935, No 65


NZLII — 🌐 NZ Gazette 1935, No 65





✨ LLM interpretation of page content

🏗️ Comparison of Old and New Standard Sizes of Conductors (continued from previous page)

🏗️ Infrastructure & Public Works
Electrical Conductors, Standards, Dimensions, Resistance, Comparison

🏗️ Flexible Cables: Dimensions and Resistance of Conductors

🏗️ Infrastructure & Public Works
Flexible Cables, Conductors, Dimensions, Resistance, Standards