THE NEW ZEALAND GAZETTE.
[No. 65
PART 63.—CERTIFICATION.
63-01. (1) After having inspected any electrical wiring work the Authorized Inspector, if satisfied that the work has been carried out in accordance with the requirements of these Regulations, shall certify in writing to the electrical supply authority, or, where there is no such authority, then to the Chief Electrical Engineer, that he has duly inspected such work and that the tests are satisfactory, and that to the best of his knowledge and belief the installation may be safely connected with the source from which electrical energy is available.
(2) Nothing in any such certificate shall relieve the owner or occupier of any premises from the obligation to bring any installation into conformity with these Regulations if on any subsequent inspection any defects are discovered which render such installation electrically hazardous.
(3) The electrical supply authority, or the Chief Electrical Engineer, as the case may be, shall, if supply is available, forthwith authorize the person undertaking the work to make the connection, or unless requested to the contrary arrange for the connection to be made.
63-02. (1) Notwithstanding anything to the contrary in the foregoing provisions of this Part of these Regulations, the electrical supply authority may, in case of urgency, permit an installation to be temporarily connected with the source from which electrical energy is available notwithstanding that any one or more of the hereinbefore prescribed insulation resistance tests have not been satisfied; provided that no such permit shall be granted unless the installation otherwise generally complies with the requirements of these Regulations and is certified by the Authorized Inspector to be reasonably free from electrical hazard, nor for a longer period than one month; unless the Chief Electrical Engineer, on the recommendation of the electrical supply authority, extends such period beyond one month.
(2) On the expiration of the period or extended period as aforesaid for which temporary connection has been so permitted the installation shall be disconnected from the source from which electrical energy is available, unless before such expiration the Authorized Inspector has issued his certificate pursuant to the last preceding regulation.
DIVISION VII.—TABLES.
TABLE I.—DIMENSIONS, WEIGHT, AND RESISTANCE OF SOLID AND STRANDED CIRCULAR CONDUCTORS.
(Standard Annealed Copper.)
| Number and Diameter (Inches) of Wires comprising Conductor. | Overall Diameter of Conductor. | Nominal Area. | Calculated Area. | Weight per 1,000 Yards of Conductor. | Resistance per 1,000 Yards at 20° F. | ||
|---|---|---|---|---|---|---|---|
| In. | Sq. in. | Sq. in. | lb. | Ohms. | Maximum allowable for Plain Wires. | Maximum allowable for Tinned Wires. | |
| 1. | 2. | 3. | 4. | 5. | 6. | 7. | 8. |
| 1/.036 | 0·036 | 0·001 | 0·001018 | 11·77 | 23·59 | 24·29 | 24·53 |
| 1/.044 | 0·044 | 0·0015 | 0·001521 | 17·58 | 15·79 | 16·26 | 16·42 |
| 3/.029 | 0·062 | 0·002 | 0·001943 | 23·37 | 12·36 | 12·61 | 12·85 |
| 3/.036 | 0·078 | 0·003 | 0·002994 | 36·02 | 8·019 | 8·180 | 8·260 |
| 1/.064 | 0·064 | 0·003 | 0·003217 | 37·20 | 7·463 | 7·637 | 7·761 |
| 7/.029 | 0·087 | 0·0045 | 0·004546 | 54·39 | 5·281 | 5·387 | 5·493 |
| 7/.036 | 0·108 | 0·007 | 0·007005 | 83·81 | 3·427 | 3·496 | 3·530 |
| 7/.044 | 0·132 | 0·01 | 0·01046 | 125·2 | 2·294 | 2·340 | 2·363 |
| 7/.052 | 0·156 | 0·0145 | 0·01462 | 174·9 | 1·643 | 1·675 | 1·692 |
| 7/.064 | 0·192 | 0·0225 | 0·02214 | 264·9 | 1·084 | 1·106 | 1·117 |
| 19/.044 | 0·220 | 0·03 | 0·02840 | 340·4 | 0·8468 | 0·8637 | 0·8721 |
| 19/.052 | 0·260 | 0·04 | 0·03960 | 475·5 | 0·6063 | 0·6184 | 0·6244 |
| 19/.064 | 0·320 | 0·06 | 0·05999 | 720·3 | 0·4002 | 0·4082 | 0·4122 |
| 19/.072 | 0·360 | 0·075 | 0·07592 | 911·6 | 0·3162 | 0·3225 | 0·3257 |
| 19/.083 | 0·415 | 0·1 | 0·1009 | 1,211·0 | 0·2380 | 0·2427 | 0·2451 |
| 37/.064 | 0·448 | 0·12 | 0·1188 | 1,403·0 | 0·2056 | 0·2097 | 0·2118 |
| 37/.072 | 0·504 | 0·15 | 0·1478 | 1,776·0 | 0·1625 | 0·1657 | 0·1673 |
| 37/.083 | 0·581 | 0·2 | 0·1964 | 2,360·0 | 0·1223 | 0·1247 | 0·1259 |
| 37/.093 | 0·651 | 0·25 | 0·2465 | 2,963·0 | 0·09735 | 0·09933 | 0·1003 |
| 37/.103 | 0·721 | 0·3 | 0·3024 | 3,535·0 | 0·07939 | 0·08098 | 0·08177 |
| 61/.093 | 0·837 | 0·4 | 0·4064 | 4,886·0 | 0·05908 | 0·06026 | 0·06085 |
| 61/.103 | 0·927 | 0·5 | 0·4985 | 5,994·0 | 0·04816 | 0·04913 | 0·04961 |
| 91/.093 | 1·023 | 0·6 | 0·6062 | 7,290·0 | 0·03961 | 0·04040 | 0·04079 |
| 91/.103 | 1·133 | 0·75 | 0·7435 | 8,942·0 | 0·03229 | 0·03294 | 0·03326 |
| 127/.093 | 1·209 | 0·85 | 0·8459 | 10,175·0 | 0·02838 | 0·02895 | 0·02923 |
| 127/.103 | 1·339 | 1·0 | 1·0376 | 12,481·0 | 0·02314 | 0·02360 | 0·02383 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1935, No 65
NZLII —
NZ Gazette 1935, No 65
✨ LLM interpretation of page content
🏗️
General Electrical Safety Standards
(continued from previous page)
🏗️ Infrastructure & Public WorksElectrical Safety, Insulating Material, British Standard Specification
🏗️ Electrical Wiring Work Certification
🏗️ Infrastructure & Public WorksElectrical Wiring, Certification, Inspection, Safety
🏗️ Temporary Electrical Installation Connection
🏗️ Infrastructure & Public WorksTemporary Connection, Electrical Installation, Urgency, Safety
🏗️ Dimensions and Resistance of Electrical Conductors
🏗️ Infrastructure & Public WorksElectrical Conductors, Dimensions, Weight, Resistance, Standards