Electricity Reliability Performance Measures




Requirement 21 (Schedule 1, Part 5)

Reliability Performance Measures

Year ended 31 March 2007

Interruptions 2008/2012 Target 2008 Target 2007 2006 2005 2004
Total interruptions 951 1,003 988 869 983 1,012
a) Planned interruptions (Class B) 510 550 543 432 463 490
b) Unplanned interruptions (Class C) 441 453 445 437 520 522

| Unplanned interruptions not restored within: | | | | | | |
| a) 3 Hours (%) | | 31.01% | 25.23% | 26.00% | | 43.00% |
| b) 24 Hours (%) | | 2.70% | 0.46% | 0.96% | | 1.72% |

Faults 2008/2012 Target 2008 Target 2007 2006 2005 2004
Faults/100km
a) Total No. of faults 9.01 9.25 9.08 8.92 9.36 10.67
b) i) 33kV line voltage
a) Total no. of faults 6.01 6.28 5.84 9.82 5.63 5.17
ii) 11kV line voltage
a) Total no. of faults 9.30 9.54 9.33 8.84 9.71 11.20

| Faults/100km of underground line | | | | | | |
| a) Total | 6.70 | 6.60 | 8.82 | | 7.22 | |
| b) 33kV | | 5.03 | 16.81 | | 6.60 | |
| c) 11kV | 6.80 | 6.61 | 9.28 | | 7.59 | |

| Faults/100km of overhead line | | | | | | |
| a) Total | | 9.86 | 9.10 | 9.44 | 11.18 | |
| b) 33kV | | 11.06 | 9.22 | 6.08 | 5.06 | |
| c) 11kV | | 9.74 | 9.20 | 9.78 | 11.81 | |

Note: ¹² substation equipment faults are now classed as underground 33kV faults

Reliability Measures 2008/2012 Target 2008 Target 2007 2006 2005 2004
Total SAIDI (Classes B & C) 153 153 140 134 156 202
SAIDI
a) Planned interruptions (Class B) 38 38 33 28 25 30
b) Unplanned interruptions (Class C) 115 115 105 106 130 171
c) Unplanned interruptions Transpower (Class D) 0.45 0.03 5

| Total SAIFI (Classes B & C) | 2.39 | 2.39 | 2.15 | 2.83 | 3.21 | 2.38 |
| SAIFI | | | | | | |
| a) Planned Interruptions (Class B)| 0.19 | 0.19 | 0.23 | 0.18 | 0.16 | 0.21 |
| b) Unplanned interruptions (Class C)| 2.20 | 2.20 | 1.92 | 2.65 | 3.05 | 2.17 |
| c) Unplanned interruptions Transpower (Class D)| 0.03 | | 0.01 | | 0.20 | |

| Total CAIDI (Classes B & C) | 64 | 64 | 63 | 47 | 48 | 85 |
| CAIDI | | | | | | |
| a) Planned interruptions (Class B)| 201 | 201 | 147 | 160 | 154 | 141 |
| b) Unplanned interruptions (Class C)| 52 | 52 | 55 | 40 | 43 | 79 |
| c) Unplanned interruptions Transpower (Class D)| 16 | | 3 | | 22 | |



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2008, No 53


Gazette.govt.nz PDF NZ Gazette 2008, No 53





✨ LLM interpretation of page content

🏭 Unison Networks Limited - Annual Valuation Reconciliation Report (continued from previous page)

🏭 Trade, Customs & Industry
Financial Statements, Assets, Valuation, Electricity Information Disclosure Requirements