β¨ Energy Performance Statistics
4 MARCH 2008 NEW ZEALAND GAZETTE, No. 50
1431
TOP ENERGY LIMITED
Performance Measures and Statistics
For the Year Ended 31 March 2007
Regulation 22
Reliability Performance Measures
i. Total number of interruptions and breakdowns by interruption class
| Class Type of Interruption | Target
| |
| 5yr Ave. | Target 2008 |
|------------------------------------------|------------|-------------|
| | 2007 | 2006 | 2005 | 2004 |
| | No | No | No | No |
| A. Planned - Transpower | 0 | 1 | 0 | 0 |
| B. Planned - Top Energy | 168 | 159 | 147 | 169 |
| C. Unplanned - Top Energy | 330 | 368 | 220 | 219 |
| D. Unplanned - Transpower | 2 | 0 | 2 | 1 |
| E. Unplanned - Embedded Generation | 0 | 0 | 0 | 0 |
| F. Unplanned - Other Generation | 0 | 0 | 0 | 0 |
| G. Unplanned - Another Line owner | 0 | 0 | 0 | 0 |
| H. Planned - Another Line owner | 0 | 0 | 0 | 0 |
| I. Any other interruption | 0 | 0 | 0 | 0 |
| Total - All interruptions | 500 | 528 | 369 | 389 |
| Class C interruptions not restored: |
| a. Within 3 hours | 7% | 30% | 46% | 42% |
| b. Within 24 hours | 2% | 2% | 2% | 1% |
ii. Number of faults per 100 circuit kms
| Line Voltage | Total |
|---|---|
| 2007 | |
| 100kV | 0.00 |
| 66kV | 0.00 |
| 33kV | 7.58 |
| 11kV | 11.46 |
| 6.6kV | 7.50 |
| 3.3kV | 0.00 |
| Total | 10.80 |
| Underground | |
|---|---|
| 2007 | |
| 100kV | 0.00 |
| 66kV | 0.00 |
| 33kV | 0.00 |
| 11kV | 0.00 |
| 6.6kV | 0.00 |
| 3.3kV | 0.00 |
| Overhead | |
|---|---|
| 2007 | |
| 100kV | 0.00 |
| 66kV | 0.00 |
| 33kV | 7.55 |
| 11kV | 10.82 |
| 6.6kV | 2.16 |
| 3.3kV | 0.00 |
| Total | 8.69 |
| Target Faults:|
| | Target | Target |
| | 5yr Ave. | 2008 |
| 33kV | 2.0 | 2.0 |
| 11kV | 7.0 | 7.5 |
| Total | 7.0 | 7.0 |
iii. Breakdown of statistics by interruption class
| Class Type of Interruption | SAIDI (Minutes) | SAIFI (Interruptions) | CAIDI (Minutes) |
|---|---|---|---|
| 2007 | 2006 | 2005 | |
| A. Planned - Transpower | 0.0 | 34.0 | 0.0 |
| B. Planned - Top Energy | 18.2 | 22.3 | 39.4 |
| C. Unplanned - Top Energy | 398.9 | 499.8 | 343.1 |
| D. Unplanned - Transpower | 70.7 | 6.0 | 113.7 |
| E. Unplanned - Embedded Generation | 0.0 | 0.0 | 0.0 |
| F. Unplanned - Other Generation | 0.0 | 0.0 | 0.0 |
| G. Unplanned - Another Line owner | 0.0 | 0.0 | 0.0 |
| H. Planned - Another Line owner | 0.0 | 0.0 | 0.0 |
| I. Any other interruption | 0.0 | 0.0 | 0.0 |
| Total - All interruptions | 487.8 | 562.1 | 496.2 |
| Targets: |
| B. Planned - Top Energy | 40 | 50 |
| C. Unplanned - Top Energy| 260| 270 |
| SAIFI Targets: |
| 5yr Ave. | 2008 |
| 4.9 | 4.9 |
| CAIDI Targets: |
| 5yr Ave. | 2008 |
| 133 | 106 |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2008, No 50
Gazette.govt.nz —
NZ Gazette 2008, No 50
β¨ LLM interpretation of page content
π
Performance Measures and Statistics of Top Energy Limited
(continued from previous page)
π Trade, Customs & IndustryFinancial performance, Efficiency measures, Energy delivery, Statistics, Top Energy Limited