β¨ Powerco Reliability Performance
1336
NEW ZEALAND GAZETTE, No. 46
3 MARCH 2008
18.07 Total Number Of Faults Per 100km Of Prescribed Voltage Overhead Line
| Nominal Voltage | 2007 Powerco Number of Faults/100km | 2006 Powerco Number of Faults/100km | 2005 Powerco Number of Faults/100km | 2004 Powerco Number of Faults/100km |
|---|---|---|---|---|
| 110kV | - | - | - | - |
| 66kV | 3.98 | 11.29 | 3.99 | 3.33 |
| 33kV | 5.79 | 5.51 | 10.12 | 10.72 |
| 22kV | 9.38 | 12.20 | 18.26 | 19.68 |
| 11kV | 14.26 | 14.22 | 12.02 | 15.14 |
| 6.6kV | 9.56 | 4.70 | 5.10 | 6.48 |
| 3.3kV | - | - | - | - |
| Total (weighted average) | 13.25 | 13.18 | 11.64 | 14.45 |
18.08 SAIDI for total interruptions
| Interruption Class | 2007 SAIDI | 2006 SAIDI | 2005 SAIDI | 2004 SAIDI |
|---|---|---|---|---|
| Total | 220.6 | 235.80 | 208.32 | 370.41 |
18.09 SAIDI
Targets for the Following Financial Year
| Interruption Class | 2008 Powerco SAIDI | 2007 Powerco SAIDI | 2006 Powerco SAIDI | 2005 Powerco SAIDI |
|---|---|---|---|---|
| Class B - Distributor Planned | 20 | 20 | 20 | 20 |
| Class C - Distributor Unplanned | 130 | 130 | 130 | 130 |
18.10 SAIDI
Targeted for the Following Financial Year and Subsequent 4 Financial Years
| Interruption Class | 2008 Powerco SAIDI | 2009-2012 Powerco SAIDI |
|---|---|---|
| Class B - Distributor Planned | 20 | 20 |
| Class C - Distributor Unplanned | 130 | 130 |
18.11 SAIDI class/fied
| Interruption Class | 2007 Powerco SAIDI | 2006 Powerco SAIDI | 2005 Powerco SAIDI | 2004 Powerco SAIDI |
|---|---|---|---|---|
| Class A - Transpower Planned | 15.59 | 5.60 | 3.03 | 12.86 |
| Class B - Distributor Planned | 17.64 | 10.60 | 11.12 | 21.93 |
| Class C - Distributor Unplanned | 164.08 | 203.00 | 183.43 | 304.35 |
| Class D - Transpower Unplanned | 21.05 | 16.60 | 9.21 | 31.04 |
| Class E - ECNZ Unplanned | - | - | - | - |
| Class F - Other Generator Unplanned | - | - | - | - |
| Class G - Other Line Owner Unplanned | - | - | - | - |
| Class H - Other Line Owner Planned | - | - | - | - |
| Class I - Other Owner (Not in A - H) | 2.24 | - | 1.53 | 0.24 |
| Total | 220.58 | 235.80 | 208.32 | 370.41 |
18.12 SAIFI for total interruptions
| Interruption Class | 2007 SAIFI | 2006 SAIFI | 2005 SAIFI | 2004 SAIFI |
|---|---|---|---|---|
| Total | 2.800 | 2.690 | 2.915 | 3.787 |
18.13 SAIFI
Targeted for the Following Financial Year
| Interruption Class | 2008 Powerco SAIFI | 2007 Powerco SAIFI | 2006 Powerco SAIFI | 2005 Powerco SAIFI |
|---|---|---|---|---|
| Class B - Distributor Planned | 0.14 | 0.14 | 0.14 | 0.14 |
| Class C - Distributor Unplanned | 2.36 | 2.36 | 2.36 | 2.36 |
18.14 SAIFI
Targeted for the Following Financial Year and Subsequent 4 Financial Years
| Interruption Class | 2008 Powerco SAIFI | 2009-2012 Powerco SAIFI |
|---|---|---|
| Class B - Distributor Planned | 0.14 | 0.14 |
| Class C - Distributor Unplanned | 2.36 | 2.36 |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2008, No 46
Gazette.govt.nz —
NZ Gazette 2008, No 46
β¨ LLM interpretation of page content
πΎ
Disclosure of Reliability Performance Measures
(continued from previous page)
πΎ Primary Industries & ResourcesReliability Performance, Interruptions, Powerco, Faults, Restoration