β¨ Electricity Reliability Performance Measures
296
NEW ZEALAND GAZETTE, No. 11
28 JANUARY 2008
DISCLOSURE OF RELIABILITY PERFORMANCE MEASURES UNDER THE ELECTRICITY INFORMATION DISCLOSURE REQUIREMENTS 2004
| 2007 | 2006 | 2005 | 2004 | 2003 | |
|---|---|---|---|---|---|
| 1. Total Number of Interruptions | |||||
| Class A - Planned - by Transpower | 0 | 0 | 1 | 1 | 0 |
| Class B - Planned - by Northpower | 208 | 211 | 251 | 149 | 160 |
| Class C - Unplanned - by Northpower | 310 | 290 | 225 | 256 | 361 |
| Class D - Unplanned - by Transpower | 1 | 1 | 1 | 0 | 2 |
| Total | 519 | 502 | 478 | 406 | 523 |
| 2. Interruption Targets for 2007/2008 | |||||
| Class B - Planned - by Northpower | 180 | ||||
| Class C - Unplanned - by Northpower | 220 | ||||
| 3. Average Interruption Targets for Next 5 Yrs | |||||
| Class B - Planned - by Northpower | 160 | ||||
| Class C - Unplanned - by Northpower | 170 | ||||
| 4. Proportion of Class C | 3 Hrs | 17.7% | 16.8% | 16.4% | 15.5% |
| Interruptions not restored within | 24 Hrs | 0% | 0% | 0% | 0% |
| 5. (a) Total No. of Faults per | 11 kV | 9.19 | 8.52 | 6.72 | 7.79 |
| 100 circuit kilometres of | 33 kV | 4.33 | 5.63 | 5.11 | 7.76 |
| prescribed voltage electric line | All | 8.87 | 8.33 | 6.61 | 7.79 |
| (b) Target for 2007/2008 Year | 11 kV | 7.30 | |||
| 33 kV | 2.00 | ||||
| All | 7.00 | ||||
| (c) Average Target for | 11 kV | 5 | |||
| next five years | 33 kV | 2 | |||
| All | 5 | ||||
| 6. Total No. of Faults per 100 circuit | 11 kV | 2.01 | 2.01 | 1.68 | 1.92 |
| kilometres of underground | 33 kV | 0.00 | 0.00 | 0.00 | 0.00 |
| prescribed voltage electric line | All | 1.82 | 1.82 | 1.48 | 1.67 |
| 7. Total No. of Faults per 100 circuit | 11 kV | 9.53 | 8.83 | 6.91 | 7.76 |
| kilometres of overhead | 33 kV | 4.65 | 6.05 | 5.48 | 7.79 |
| prescribed voltage electric line | All | 9.22 | 8.65 | 6.82 | 7.79 |
| 8. The SAIDI for the total No. of Interruptions | 151.33 | 119.23 | 113.24 | 145.32 | |
| 9. SAIDI Targets for 2007/08 | |||||
| Class B - Planned - by Line Owners | 30 | ||||
| Class C - Unplanned - by Line Owners | 87 | ||||
| 10. Average SAIDI Target for next five years | |||||
| Class B - Planned - by Line Owners | 30 | ||||
| Class C - Unplanned - by Line Owners | 85 |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2008, No 11
Gazette.govt.nz —
NZ Gazette 2008, No 11
β¨ LLM interpretation of page content
π
Disclosure of Reliability Performance Measures Under the Electricity Information Disclosure Requirements 2004
(continued from previous page)
π Trade, Customs & IndustryElectricity, Reliability, Interruptions, Performance Measures, Northpower, Transpower