✨ Amendments to Hazardous Substances Regulations
27 JUNE 2006
NEW ZEALAND GAZETTE, No. 70
1627
Clause 15(2)
In paragraph (c), omit "." and substitute "; or" and insert the following:
(d) a paint mixing room that complies with AS/NZS 4114.
Clause 16
In subclause (1), omit "type 1, or type 2, or type 3 building" and substitute "type of building specified in subclauses 15(2)(a) to (d)".
In subclause (2)(a), after the second reference to "building", insert "or paint mixing room that complies with AS/NZS 4114".
Clause 20(1A)
Omit "Cylinders" and substitute "For cylinders".
Clause 20(2)
Immediately after "greater than 100kg", omit "or more".
Clause 21
Immediately after paragraph (b), insert "Notwithstanding the above, a tank fill zone need not be separated from the boundary of the controlled zone by any more than 15 metres".
New clauses 25A and 25B
Immediately after clause 25, insert the following:
25A Storage of packages holding class 3.1 hazardous substances in a store in a building
(1) Substances of hazard classification 3.1 may be situated in a store inside a building provided that they are stored—
(a) in a room with the walls and ceiling constructed with a 60/60/60 fire resistance rating and—
(i) not more than 450 litres is situated in the store; and
(ii) the substances are stored in containers, each not exceeding 20 litres capacity; or
(b) in a room with the walls and ceiling constructed of reinforced concrete or equivalent with a 120/120/120 fire resistance rating and—
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2006, No 70
Gazette.govt.nz —
NZ Gazette 2006, No 70
✨ LLM interpretation of page content
🏥
Amendments to Schedule 10 of the principal notice
(continued from previous page)
🏥 Health & Social WelfareAmendments, Hazardous Substances, Building Standards, Fire Resistance, Storage Regulations, Paint Mixing Rooms, Tank Fill Zones, Class 3.1 Substances