✨ Hazardous Substances Regulations
1590 NEW ZEALAND GAZETTE, No. 67 26 JUNE 2006
(i) 5% of the total pooling potential; or
(ii) 5,000 litres.
(3) Pooling substances to which subclause (2) applies must be segregated where
appropriate to ensure that leakage of one substance may not adversely affect
the container of another substance.
Regulation 38 This regulation applies to each hazardous substance described in Schedule 1, as if
the following subclauses were inserted at the end:
(2) If pooling substances which do not have class 1 to 5 hazard classifications
are held in a place above ground in containers 1 or more of which has a
capacity of more than 60 litres but none of which has a capacity of more
than 450 litres—
(a) if the place’s total pooling potential is less than 20,000 litres, the
secondary containment system must have a capacity of either 25% of
that total pooling potential or 110% of the capacity of the largest
container, whichever is the greater:
(b) if the place’s total pooling potential is 20,000 litres or more, the
secondary containment system must have a capacity of the greater
of—
(i) 5% of the total pooling potential; or
(ii) 5,000 litres.
(3) Pooling substances to which subclause (2) applies must be segregated where
appropriate to ensure that the leakage of one substance may not adversely
affect the container of another substance.
Control – Schedule 8 of the Hazardous Substances (Dangerous Goods and Scheduled Toxic
Substances) Transfer Notice 2004
Clause 100
In subclause (1)(b) of the change to controls for clause 100, omit "Table" and substitute "Schedule".
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2006, No 67
Gazette.govt.nz —
NZ Gazette 2006, No 67
✨ LLM interpretation of page content
🏥
Hazardous Substances (Classes 6, 8, and 9 Controls) Regulations 2001
(continued from previous page)
🏥 Health & Social WelfareHazardous Substances, Regulations, Transportation, Veterinary Medicines, Approved Handler, Safety System, Land Transport, Rail, Sea, Air