β¨ Electricity Reliability Performance Measures
Requirement 21 (Schedule 1, Part 5)
Reliability Performance Measures
Year ended 31 March 2006
Interruptions
| 2007/10 Target | 2007 Target | 2006 | 2005 | 2004 | 2003 | |
|---|---|---|---|---|---|---|
| Total interruptions | 869 | 983 | 1,012 | 583 | ||
| a) Planned interruptions (Class B) | 432 | 463 | 490 | 324 | ||
| b) Unplanned interruptions (Class C) | 437 | 520 | 522 | 259 |
Unplanned interruptions not restored within:
| | | | | | | |
| a) 3 Hours (%) | | | 25.23% | 26.00% | 43.00% | 29.00%|
| b) 24 Hours (%) | | | 0.46% | 0.96% | 1.72% | 0.39% |
Faults
| 2007/10 Target | 2007 Target | 2006 | 2005 | 2004 | 2003 | |
|---|---|---|---|---|---|---|
| Faults/100km | ||||||
| a) Total No. of faults | 9.80 | 9.80 | 8.92 | 9.38 | 10.67 | 8.96 |
| b) Next year targets | ||||||
| c) Next 5 year average target | ||||||
| d) i) 33kV line voltage | ||||||
| a) Total no. of faults | 9.82 | 5.63 | 5.17 | 3.58 | ||
| b) Next year target | ||||||
| c) Next 5 year target | ||||||
| ii) 11kV line voltage | ||||||
| a) Total no. of faults | 8.84 | 9.71 | 11.20 | 8.89 | ||
| b) Next year target | ||||||
| c) Next 5 year target |
Faults/100km of underground line
| | | | 2006 | 2005 | 2004 | 2003 |
|------------------------|----------------|-------------|---------|--------|---------|--------|
| a) Total | 7.30 | 7.30 | 6.60 | 8.82 | 7.22 | 10.06 |
| b) 33kV | | | 16.81 | - | *6.60 | - |
| c) 11kV | | | 6.61 | 9.28 | 7.58 | 10.06 |
Faults/100km of overhead line
| | | | 2006 | 2005 | 2004 | 2003 |
|------------------------|----------------|-------------|---------|--------|---------|--------|
| a) Total | 10.00 | 10.00 | 9.10 | 9.44 | 11.18 | 12.52 |
| b) 33kV | | | 9.22 | 6.08 | 5.66 | 3.20 |
| c) 11kV* | | | 9.20 | 9.78 | 11.81 | 9.31 |
*Note: 2 substation equipment faults are now classified as underground 33kV faults.
Reliability Measures
| 2007/10 Target | 2007 Target | 2006 | 2005 | 2004 | 2003 | |
|---|---|---|---|---|---|---|
| Total SAIDI (Classes B & C) | 153 | 153 | 134 | 156 | 202 | 97 |
| SAIDI | ||||||
| a) Planned interruptions (Class B) | 38 | 38 | 28 | 25 | 30 | 25 |
| b) Unplanned interruptions (Class C) | 115 | 115 | 106 | 130 | 171 | 72 |
| c) Unplanned interruptions Transpower (Class D) | 0.03 | 5 | - | - |
| Total SAIFI (Classes B & C) | 2.40 | 2.40 | 2.83 | 3.21 | 2.38 | 2.02 |
| SAIFI | | | | | | |
| a) Planned Interruptions (Class B) | 0.20 | 0.20 | 0.18 | 0.16 | 0.21 | 0.22 |
| b) Unplanned interruptions (Class C)| 2.20 | 2.20 | 2.65 | 3.05 | 2.17 | 1.80 |
| c) Unplanned interruptions Transpower (Class D) | | | 0.01 | 0.20 | - | - |
| Total CAIDI (Classes B & C) | 243 | 243 | 47 | 48 | 85 | 67 |
| CAIDI | | | | | | |
| a) Planned interruptions (Class B) | 191 | 191 | 160 | 154 | 141 | 172 |
| b) Unplanned interruptions (Class C)| 52 | 52 | 40 | 43 | 79 | 56 |
| c) Unplanned interruptions Transpower (Class D) | | | 3 | 22 | - | - |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2006, No 157
Gazette.govt.nz —
NZ Gazette 2006, No 157
β¨ LLM interpretation of page content
π
Financial and Efficiency Performance Measures for Unison Networks Limited
(continued from previous page)
π Trade, Customs & IndustryFinancial measures, Efficiency measures, Return on funds, Return on equity, Return on investment, Direct line cost, Indirect line cost, Electricity information disclosure, Unison Networks Limited
π Reliability Performance Measures for Unison Networks Limited
π Trade, Customs & IndustryElectricity reliability, Interruptions, Faults, SAIDI, SAIFI, CAIDI, Unison Networks Limited