β¨ Electricity Reliability Statistics
4214 NEW ZEALAND GAZETTE, No. 146 22 NOVEMBER 2006
6 Faults per 100 circuit-km of underground electric line:
| 2006 | 2005 | 2004 | 2003 | |
|---|---|---|---|---|
| 66kV | 1.6 | 1.6 | 0.0 | 3.2 |
| 33kV | 4.0 | 4.0 | 4.5 | 0.0 |
| 11kV | 2.8 | 3.1 | 3.3 | 2.6 |
| All | 2.7 | 3.1 | 3.2 | 2.6 |
7 Faults per 100 circuit-km of overhead electric line:
| 2006 | 2005 | 2004 | 2003 | |
|---|---|---|---|---|
| 66kV | 2.5 | 1.0 | 0 | 5.3 |
| 33kV | 2.8 | 3.8 | 1.9 | 4.2 |
| 11kV | 13.3 | 11.8 | 10.3 | 16.9 |
| All | 12.0 | 10.8 | 9.3 | 15.5 |
8, 11,
12, 15,
16, 19 SAIDI, SAIFI and CAIDI by interruption class and in total for 2006:
| Network or generation owner | Interruption class | Classification of interruptions | | SAIDI (minutes per connected consumer) | | SAIFI (interruptions per connected consumer) | | CAIDI (minutes per consumer interrupted) |
|-----------------------------|--------------------|----------------------------------| |-----------------------------------------| |-------------------------------------------------------------| |---------------------------------------------------------------|
| Orion | B | Planned shutdowns | 6.0 | 0.02 | 238 |
| Orion | C | Unplanned cuts | 53.3 | 0.72 | 75 |
| | | | 59.3 | 0.74 | 80 |
| Transpower | A | Planned shutdowns | 0.0 | 0.00 | 0 |
| Transpower | D | Unplanned cuts | 4.7 | 0.22 | 21 |
| | | | 4.7 | 0.22 | 21 |
| | | Total | 64.0 | 0.96 | 67 |
8, 11,
12, 15,
16, 19 SAIDI, SAIFI and CAIDI by interruption class and in total for 2005:
| Network or generation owner | Interruption class | Classification of interruptions | | SAIDI (minutes per connected consumer) | | SAIFI (interruptions per connected consumer) | | CAIDI (minutes per consumer interrupted) |
|-----------------------------|--------------------|----------------------------------| |-----------------------------------------| |-------------------------------------------------------------| |---------------------------------------------------------------|
| Orion | B | Planned shutdowns | 7.7 | 0.03 | 286 |
| Orion | C | Unplanned cuts | 44.0 | 0.71 | 62 |
| | | | 51.7 | 0.74 | 70 |
| Transpower | A | Planned shutdowns | 0.2 | 0.00 | 195 |
| Transpower | D | Unplanned cuts | 1.0 | 0.02 | 46 |
| | | | 1.2 | 0.02 | 55 |
| | | Total | 52.9 | 0.76 | 70 |
Next Page →
Online Sources for this page: