β¨ Electricity Reliability Performance Measures
DISCLOSURE OF RELIABILITY PERFORMANCE MEASURES UNDER THE ELECTRICITY INFORMATION DISCLOSURE REQUIREMENTS 2004
17 JANUARY 2005
NEW ZEALAND GAZETTE, No. 9
207
1. Total Number of Interruptions
|
2004 |
2003 |
2002 |
2001 |
| Class A - Planned - by Transpower |
1 |
0 |
1 |
0 |
| Class B - Planned - by Northpower |
149 |
160 |
225 |
209 |
| Class C - Unplanned - by Northpower |
256 |
361 |
271 |
312 |
| Class D - Unplanned - by Transpower |
0 |
2 |
0 |
2 |
| Total |
406 |
523 |
497 |
523 |
2. Interruption Targets for 2004/2005
|
2004 |
2003 |
2002 |
2001 |
| Class B - Planned - by Northpower |
180 |
200 |
210 |
220 |
| Class C - Unplanned - by Northpower |
240 |
240 |
240 |
250 |
3. Average Interruption Targets for Next 5 Yrs
|
2004/05-2008/09 |
| Class B - Planned - by Northpower |
160 |
|
2003/04-2007/08 |
|
170 |
|
2002/03-2006/07 |
|
180 |
|
2001/02-2005/06 |
|
200 |
| Class C - Unplanned - by Northpower |
170 |
|
190 |
|
190 |
|
200 |
4. Proportion of Class C Interruptions not restored within
| 3 Hrs | 15.5% | 15.7% | 14.4% | 15.7% |
| 24 Hrs | 0% | 0% | 0% | 0% |
5. (a) Total No. of Faults per 100 circuit kilometres of prescribed voltage electric line
|
2004 |
2003 |
2002 |
2001 |
| 11 kV |
7.79 |
10.74 |
8.54 |
9.51 |
| 33 kV |
7.76 |
9.57 |
2.17 |
6.73 |
| Total |
7.79 |
10.66 |
8.11 |
9.34 |
(b) Target for 2004/2005 Year
|
2004/05 |
| 11 kV |
7.30 |
| 33 kV |
2.00 |
| Total |
7.00 |
(c) Average Target for 2004/2005 to 2008/2009 years
|
2004/05-2008/09 |
| 11 kV |
5 |
| 33 kV |
2 |
| Total |
5 |
6. Total No. of Faults per 100 circuit kilometres of underground prescribed voltage electric line
|
2004 |
2003 |
2002 |
2001 |
| 11 kV |
1.92 |
1.03 |
2.30 |
2.56 |
| 33 kV |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
1.67 |
0.88 |
1.92 |
2.20 |
7. Total No. of Faults per 100 circuit kilometres of overhead prescribed voltage electric line
|
2004 |
2003 |
2002 |
2001 |
| 11 kV |
7.76 |
11.04 |
8.72 |
9.69 |
| 33 kV |
7.79 |
10.33 |
2.35 |
7.18 |
| Total |
7.79 |
11.00 |
8.31 |
9.54 |
8. The SAIDI for the total No. of Interruptions
| 2004 |
| 145.32 |
| 2003 |
| 181.83 |
| 2002 |
| 219.86 |
| 2001 |
| 182.52 |
9. SAIDI Targets for 2004/05
| Class |
2004/05 |
| Class B - Planned - by Line Owners |
30 |
| Class C - Unplanned - by Line Owners |
95 |
10. Average SAIDI Target for 2004/5 to 2008/9 Yrs
| Class |
2004/05-2008/09 |
| Class B - Planned - by Line Owners |
30 |
| Class C - Unplanned - by Line Owners |
85 |
Next Page →
Online Sources for this page:
β¨ LLM interpretation of page content
π
Disclosure of Reliability Performance Measures under Electricity Information Disclosure Requirements 2004
(continued from previous page)
π Trade, Customs & Industry
17 January 2005
Electricity, Reliability, Performance Measures, Interruptions, Faults, SAIDI, Northpower, Transpower