Amendments to Hazardous Substances Regulations




16 DECEMBER 2005

NEW ZEALAND GAZETTE, No. 208

5309

New clause 21A

Insert, after clause 21, the following new subclause:

21A Separation of cylinder filling stations for class 2.1.1 liquefiable gas from boundary of controlled zone

Cylinder filling stations are to be installed so as to ensure a separation distance of at least–

(a) 15 metres from an area of high intensity or low intensity land use, where the quantity of class 2.1.1A [liquefiable gas stored in cylinders at the filling station is 1,000 kg or greater; or

(b) 8 metres from an area of high intensity or low intensity land use, where the quantity of class 2.1.1A liquefiable gas stored in cylinders at the filling station is more than 100 kg but less than 1,000 kg; or

(c) 6 metres from an area of high intensity land use and 3 metres from an area of low intensity land use where the quantity of class 2.1.1A liquefiable gas stored in cylinders at the filling station, is less than 100kg.

Heading to clause 22

Insert, after the words \"flammable aerosols\", the words \"and threaded or self-sealing gas cartridges of LPG\".

Clause 22(1)

Insert, after the words \"flammable aerosols\", the words \"and threaded or self-sealing gas cartridges of LPG of up to 1,000 ml water capacity manufactured to EN 417 or other approved standards,\" and omit the words \"to which this Part applies\".

Clause 23

Repeal subclause (1) and substitute the following new subclause:

(1) This clause does not apply to–

(a) a domestic oil-burning installation that–

(i) includes a stationary tank that has a capacity that does not exceed 1,200 litres; and

(ii) complies with clause 64 of Schedule 8 of this notice; or

(b) a stationary tank that complies with clause 62(3)(b) of Schedule 8 of this notice.

Insert, after subclause (2), the following new subclause:

(3) Where an above ground stationary tank, transportable container or tank wagon, having multiple compartments is installed, the separation distance to areas of high intensity land use and low intensity land use will be based on the aggregate volume of the compartments and the lowest flash point substance stored in any of the compartments.

Clause 24(3)

Omit in subclause (a), the expression \"section 4.5\" and insert \"section 4.9\".

Clause 28(2)

Insert, after the words \"clause applies\", the words \",and which are located in a building,\".



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2005, No 208


Gazette.govt.nz PDF NZ Gazette 2005, No 208





✨ LLM interpretation of page content

🏥 Amendments to Schedule 10 to the principal notice (continued from previous page)

🏥 Health & Social Welfare
Hazardous Substances, Emergency Management Regulations, Schedule Amendments, Definitions, Storage Requirements