✨ Reliability Performance Measures




Reliability Performance Measures (Requirement 21)

CAIDI

Class Average CAIDI Targets CAIDI Targets Actual CAIDI
2006/10 2005 2004

CAIDI for total number of interruptions (= a/b)

where -

a = sum of interruption duration factors for all interruptions
b = sum of electricity consumers affected by each of those interruptions

| | | 133 | 127 | 134 | 68 |

CAIDI Targets

Planned Interruptions

Class B

| | 133 | 143 |

Unplanned Interruptions

Class C

| | 129 | 142 |

where -

Planned interruptions

a = sum of interruption duration factors for all interruptions
b = projected number of electricity consumers affected by each of those interruptions

| Class B | 994,240 | 1,068,808 |

| | 7,457 | 7,457 |

Unplanned interruptions

a = sum of interruption duration factors for all interruptions
b = projected number of electricity consumers affected by each of those interruptions

| Class C | 5,365,370 | 6,015,752 |

| | 42,255 | 42,255 |

CAIDI for total number of interruptions within each interruption class (= a/b)

Class 2006/10 2005 2004 2003 2002
Class A 0 0 210 312 DNV0
Class B 196 161 147 256 -
Class C 130 169 113 49 -
Class D 309 22 309 0 -
Class E 0 0 0 0 -
Class F 0 0 0 0 -
Class G 0 154 0 0 -
Class H 0 0 0 0 -
Class I 0 0 0 0 -

CAIDI for total of interruptions

where -
a = sum of interruption duration factors for all interruptions

| | 133 | 127 | 134 | 68 |

| Class A | 0 | 78,750 | 587,769 | -
| Class B | 766,018 | 846,417 | 1,436,653| 1,398,160 |
| Class C | 6,204,120| 7,344,384 | 7,213,916| 2,861,194 |
| Class D | 50,694 | 77,041 | 1,545,203| 48,870 |
| Class E | 0 | 0 | 0 | 0 |
| Class F | 0 | 0 | 0 | 0 |
| Class G | 0 | 27,721 | 0 | 0 |
| Class H | 0 | 0 | 0 | 0 |
| Class I | 0 | 0 | 0 | 0 |

b = sum of electricity consumers affected by each of those interruptions within that interruption class

| Class A | 0 | 375 | 1,883 | -
| Class B | 4,723 | 6,025 | 9,795 | 7,478 |
| Class C | 47,724 | 43,485 | 64,049 | 56,178 |
| Class D | 497 | 1,279 | 5,000 | 5,430 |
| Class E | 0 | 0 | 0 | 0 |
| Class F | 0 | 0 | 0 | 0 |
| Class G | 0 | 180 | 0 | 0 |
| Class H | 0 | 0 | 0 | 0 |
| Class I | 0 | 0 | 0 | 0 |



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2005, No 149