NEW ZEALAND GAZETTE, No. 122

10 AUGUST 2005

Buller Electricity Limited

Line Business Performance Measures

Disclosure of energy delivery efficiency performance measures under requirement 20 of the Electricity Information Disclosure Requirements 2004.

1 Energy Delivery efficiency performance measures:

(a) Load Factor (=a/b*c*100)

    a = kWh of electricity entering system    45,629,456    44,037,981*    42,764,385*    44,532,248*
    b = Maximum demand                     7,903         7,820*         7,749*         8,062*
    c = Total number of hours in year        8,760         8,784          8,760          8,760

(b) Loss Ratio (=a/b*100)

    a = losses in electricity in kWh       4,460,951     3,955,387*     4,893,797*     4,289,870*
    b = kWh of electricity entering system 45,629,456    44,037,981*    42,764,385*    44,532,248*

(c) Capacity Utilisation (=a/b*100)

    a = Maximum demand                   7,903         7,820*         7,749*         8,062*
    b = Transformer Capacity             28,735        28,550         28,775         27,650

2 Statistics

(a) System Length (Total) (kms)

    Circuit Kilometres 110kV             2             1              0              0
    Circuit Kilometres 33kV               101           103            111            111
    Circuit Kilometres 11kV               367           374            357            355
    Circuit Kilometres 400V               128           130            130            129

    Total                             598           608            598            595

(b) Circuit Length (Overhead) (kms)

    Circuit Kilometres 110kV             2             1              0              0
    Circuit Kilometres 33kV               101           103            111            111
    Circuit Kilometres 11kV               360           370            351            350
    Circuit Kilometres 400V               118           118            118            117

    Total Overhead                    581           592            580            578

(c) Circuit Length (Underground) (kms)

    Circuit Kilometres 110kV             0.0           0.0            0.0            0.0
    Circuit Kilometres 33kV               0.2           0.2            0.2            0.2
    Circuit Kilometres 11kV               7.0           4.2            5.0            4.7
    Circuit Kilometres 400V               10.0          11.8           11.6           11.5

    Total Underground                 17.2          16.2           16.8           16.4

(d) Transformer Capacity (In Kilovolt Amperes)

                                    28,735        28,550         28,775         27,650

(e) Maximum Demand (kW)

                                    7,903         7,820*         7,749*         8,062*

LexisNexis



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2005, No 122


Gazette.govt.nz PDF NZ Gazette 2005, No 122





✨ LLM interpretation of page content

🏭 Buller Electricity Limited Line Business Performance Measures (continued from previous page)

🏭 Trade, Customs & Industry
Electricity Delivery, Efficiency Measures, Load Factor, Loss Ratio, Capacity Utilisation, System Length, Transformer Capacity, Maximum Demand