✨ Hazardous Substances Tables




26 MARCH

NEW ZEALAND GAZETTE

(2) The table referred to in clauses 7 and 20 is:

Aggregate quantity of liquefiable gas in cylinders only (kg) Area of high intensity land use (metres) Area of low intensity land use (metres)
Up to 100 0 0
250 2 0
500 2 2
2,000 3 2
5,000 5 3
10,000 7 4
50,000 8 5
More than 50,000 15 8

(3) The table referred to in clauses 8 and 21 is:

Water capacity of tank (litres) Area of high intensity land use (metres) Area of low intensity land use (metres)
Up to 500 2 2
1,000 3 3
5,000 8 5
10,000 11 7
20,000 15 9
50,000 17 10
100,000 21 12
200,000 or more 28 14


Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2004, No 35


Gazette.govt.nz PDF NZ Gazette 2004, No 35





✨ LLM interpretation of page content

🌾 Separation of building holding package containing class 3.1 hazardous substance from boundary of controlled zone (continued from previous page)

🌾 Primary Industries & Resources
Hazardous Substances, Class 3.1A, Class 3.1B, Class 3.1C, Controlled Zone, Building Separation, Storage Requirements, High Intensity Land Use, Low Intensity Land Use, Distance Calculations