✨ Electricity Reliability Performance Measures




27 JUNE

NEW ZEALAND GAZETTE

1949


8 SAIDI for total of interruptions during :

2002 2001 2000 1999
SAIDI 564.2 573.6 472.8 588.9

9 SAIDI targets for the following year
10 and for the subsequent four financial years

2003 2004 2005 2006 2007 Average 2003/07
Planned (TLC) 155.0 110.0 90.0 81.0 73.0 101.8
Unplanned (TLC) 230.0 210.0 180.0 162.0 146.0 185.6

11 SAIDI according to class

2002 2001 2000 1999
Planned (Transpower) 41.0 13.3 0.0 0.0
Planned (TLC) 199.3 207.7 203.4 239.5
Unplanned (TLC) 265.0 321.2 242.4 329.7
Unplanned (Transpower) 58.9 28.0 27.0 19.7
Generation (Others) 0.0 3.4 0.0 0.0

12 SAIFI for total of interruptions during :

2002 2001 2000 1999
SAIFI 6.55 6.51 7.34 8.88

13 SAIFI targets for the following year
14 and for the subsequent four financial years

2003 2004 2005 2006 2007 Average 2003/07
Planned (TLC) 0.7 0.5 0.4 0.4 0.3 0.5
Unplanned (TLC) 3.8 3.2 2.6 2.3 2.1 2.8

15 SAIFI according to class

2002 2001 2000 1999
Planned (Transpower) 0.21 0.06 0.00 0.00
Planned (TLC) 0.95 1.12 0.91 1.25
Unplanned (TLC) 4.44 4.42 5.25 6.43
Unplanned (Transpower) 0.95 0.78 1.18 1.20
Generation (Others) 0.00 0.13 0.00 0.00

16 CAIDI for total of interruptions during :

2002 2001 2000 1999
CAIDI 86.1 88.1 64.4 66.3

17 CAIDI targets for the following year
18 and for the subsequent four financial years

2003 2004 2005 2006 2007 Average 2003/07
Planned (TLC) 221.4 220.0 225.0 225.0 225.0 223.3
Unplanned (TLC) 60.5 65.6 69.2 69.2 69.2 66.8

19 CAIDI according to class

2002 2001 2000 1999
Planned (Transpower) 193.1 240.0 0.0 0.0
Planned (TLC) 210.2 184.8 223.5 191.6
Unplanned (TLC) 59.7 72.7 46.2 51.3
Unplanned (Transpower) 62.3 35.8 22.9 16.4
Generation (Others) 0.0 25.5 0.0 0.0

LexisNexis



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2003, No 74


Gazette.govt.nz PDF NZ Gazette 2003, No 74





✨ LLM interpretation of page content

πŸ—οΈ Reliability Performance Measures for The Lines Company Limited (continued from previous page)

πŸ—οΈ Infrastructure & Public Works
Electricity, Interruptions, Faults, Performance Measures, The Lines Company Limited