β¨ Electricity Performance Statistics
WESTPOWER LIMITED - LINES BUSINESS
3 Average interruption targets for 2003/2004 to 2007/2008 years
Class B - Planned - by Line Owners 60
Class C - Unplanned - by Line Owners 60
4 Proportion of Class C interruptions not restored within: (=(a/b)*100)
3 Hours
a = number of interruptions not restored within 3 hours 8
b = total number of Class C interruptions 57
14.0%
24 Hours
a = number of interruptions not restored within 24 hours 0
b = total number of Class C interruptions 57
0.0%
| 2003 | 2002 | 2001 | 2000 |
|---|
5 (a) The total number of faults per 100 circuit kilometres of prescribed voltage electric line
66kV 2 0 0 2
33kV 3 5 7 4
11kV 8 3 7 5
Total 6 3 7 4
(b) Target for 2003 / 2004 year
66kV 1
33kV 3
11kV 7
Total 5.3
(c) Average Target for 2003 / 2004 to 2006 / 2008 years
66kV 1
33kV 3
11kV 7
Total 5.3
6 The total number of faults per 100 circuit kilometres of underground prescribed voltage electric line
33kV 0 0 0 0
11kV 9 6 0 28
Total 9 6 0 28
7 The total number faults per 100 circuit kilometres of overhead prescribed voltage electric line
66kV 2 2 0 0
33kV 2 5 7 4
11kV 8 3 7 5
Total 6 3 7 4
8 The SAIDI for the total number of interruption
122.02 140.27 235.18 156.46
9 SAIDI targets for 2003 / 2004
Class B - Planned - by Line Owners 40
Class C - Unplanned - by Line Owners 70
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2003, No 127
Gazette.govt.nz —
NZ Gazette 2003, No 127
β¨ LLM interpretation of page content
π
Performance Measures for Westpower Limited
(continued from previous page)
π Trade, Customs & IndustryElectricity, Performance, Interruptions, Faults, SAIDI