✨ Electricity Reliability Statistics




2852

NEW ZEALAND GAZETTE

No. 108

THE POWER COMPANY LIMITED LINE BUSINESS
RELIABILITY PERFORMANCE MEASURES

PURSUANT TO REGULATION 22 OF THE ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1999 AS AMENDED BY THE ELECTRICITY (INFORMATION DISCLOSURE) AMENDMENT REGULATIONS 2000

RELIABILITY STATISTICS FOR YEARS ENDING 31 MARCH 2000, 2001, 2002 AND 2003

Class A B C D E F G H I TOTAL
Interruptions
1999/00 0 424 488 1 0 1 2 0 0 916
2000/01 0 177 389 0 0 2 0 0 0 568
2001/02 0 194 375 0 0 1 0 0 0 570
2002/03 0 149 388 0 0 3 0 0 0 540
Predicted 2003/2004 167 370
5-Year Average Target 164 365
SAIDI
1999/00 0 73.9 339.6 51.3 0 1.1 0.6 0 0 466.4
2000/01 0 16.0 130.0 0 0 0.5 0 0 0 146.5
2001/02 0 20.0 117.8 0 0 1.3 0 0 0 139.0
2002/03 0 18.9 147.8 0 0 0.3 0 0 0 167.0
Predicted 2003/2004 18.0 140.0
5-Year Average Target 18.0 135.0
SAIFI
1999/00 0 0.56 5.89 0.28 0 0.04 0.01 0 0 6.78
2000/01 0 0.13 2.76 0 0 0.01 0 0 0 2.90
2001/02 0 0.14 2.73 0 0 0.01 0 0 0 2.88
2002/03 0 0.11 3.22 0 0 0.01 0 0 0 3.33
Predicted 2003/2004 0.12 3.00
5-Year Average Target 0.12 2.90
CAIDI
1999/00 0 131.9 57.7 180.9 0 30.0 44.4 0 0 68.8
2000/01 0 120.5 47.1 0 0 80.0 0 0 0 50.5
2001/02 0 146.8 43.1 0 0 161.0 0 0 0 48.3
2002/03 0 174.4 45.9 0 0 40.3 0 0 0 50.1
Predicted 2003/2004 150.0 46.7
5-Year Average Target 150.0 46.5

Faults by Voltage

66kV 33kV 11kV Total
OH per 100km
1999/00 2.33 6.20 7.79 7.44
2000/01 1.52 2.60 6.52 5.99
2001/02 2.31 1.15 6.27 5.68
2002/03 1.14 2.27 6.65 6.03

| UG per 100km | | | | |
| 1999/00 | 0 | 0 | 8.50 | 8.20 |
| 2000/01 | 0 | 0 | 8.13 | 7.82 |
| 2001/02 | 0 | 0 | 1.93 | 1.86 |
| 2002/03 | 0 | 0 | 3.65 | 3.47 |

| Total per 100km | | | | |
| 1999/00 | 2.33 | 6.18 | 7.80 | 7.45 |
| 2000/01 | 1.52 | 2.59 | 6.54 | 6.00 |
| 2001/02 | 2.31 | 1.14 | 6.24 | 5.65 |
| 2002/03 | 1.14 | 2.25 | 6.62 | 6.00 |
| Predicted 2003/2004 | 1.70 | 1.60 | 6.30 | 5.70 |
| 5-Year Average Target | 1.70 | 1.80 | 6.10 | 5.56 |

Class C Interruptions Not Restored in 3 hours 2.3%
Class C Interruptions Not Restored in 24 hours 0%


Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2003, No 108


Gazette.govt.nz PDF NZ Gazette 2003, No 108





✨ LLM interpretation of page content

🏭 Reliability Performance Measures for The Power Company Limited (continued from previous page)

🏭 Trade, Customs & Industry
Electricity, Reliability Statistics, Interruptions, SAIDI, SAIFI, CAIDI, Faults by Voltage