β¨ Electricity Performance Statistics
19 AUGUST NEW ZEALAND GAZETTE 2809
4 Fault Restoration Times (Class C) interruptions not restored within:
|
2003 |
2002 |
2001 |
2000 |
| 3 Hours |
24.57% |
32.68% |
20.21% |
4.88% |
| 24 Hours |
1.71% |
0.65% |
0% |
0% |
5 Number of faults per 100 km of prescribed voltage line
(a) Total number of faults
|
2003 |
2002 |
2001 |
2000 |
| 66 kV |
3.1 |
3.8 |
6.5 |
6.3 |
| 33 kV |
1.3 |
1.6 |
1.2 |
3.2 |
| 22 kV |
16.3 |
14.1 |
13.9 |
4.0 |
| 11 kV |
14.0 |
6.3 |
8.7 |
6.3 |
| Total |
11.0 |
5.9 |
7.5 |
5.1 |
(b) Target for (next year)
|
2003 Target |
| 66 kV |
2.0 |
| 33 kV |
2.0 |
| 22 kV |
7.0 |
| 11 kV |
7.0 |
| Total |
5.4 |
(c) Average Target (5 years)
|
Average Target |
| 66 kV |
2.0 |
| 33 kV |
2.0 |
| 22 kV |
7.0 |
| 11 kV |
7.0 |
| Total |
5.4 |
6 The total number of faults per 100km of prescribed voltage underground line
|
2003 |
2002 |
2001 |
2000 |
| 66 kV |
0 |
0 |
0 |
0 |
| 33 kV |
0 |
0 |
0 |
0 |
| 22 kV |
0 |
0 |
0 |
0 |
| 11 kV |
2.2 |
0 |
5.2 |
3.0 |
| Total |
0.7 |
0 |
1.6 |
1.0 |
7 The total number of faults per 100km of prescribed voltage overhead line
|
2003 |
2002 |
2001 |
2000 |
| 66 kV |
3.2 |
3.8 |
6.7 |
6.7 |
| 33 kV |
1.4 |
1.6 |
1.3 |
3.2 |
| 22 kV |
16.4 |
14.2 |
14.0 |
4.0 |
| 11 kV |
14.7 |
6.6 |
8.9 |
6.4 |
| Total |
12.2 |
6.6 |
8.1 |
5.4 |
8 SAIDI for the total number of interruptions
9 SAIDI targets (next year)
| Class |
Target |
| B - Planned by Line Owner |
85 |
| C - Unplanned by Line Owner |
95 |
Next Page →