β¨ Electricity Reliability Performance Measures
Regulation 22
Disclosure by line owners (other than Transpower) of reliability performance measures
1 Total number of interruptions:
| Network or Generation Owner | Disclosure Regulation Class | Classification of Interruptions | 2003 | 2002 | 2001 | 2000 |
|---|---|---|---|---|---|---|
| Orion | B | Planned Shutdowns | 356 | 220 | 162 | 313 |
| C | Unplanned Cuts | 611 | 404 | 499 | 545 | |
| Transpower | A | Planned Shutdowns | 0 | 0 | 0 | 3 |
| D | Unplanned Cuts | 4 | 2 | 3 | 1 |
Total Interruptions | 971 | 626 | 664 | 862 |
Disclosure Regulation classes E, F and G do not apply to Orion and consequently results are all zero.
2 & 3 Interruption targets:
| Network or Generation Owner | Disclosure Regulation Class | Classification of Interruptions | 2004 | Average 2004 - 2008 |
|---|---|---|---|---|
| Orion | B | Planned Shutdowns | 385 | 385 |
| C | Unplanned Cuts | 555 | 555 |
4 Proportion of Class C interruptions not restored within:
(a) 3 hours 25.37%
(b) 24 hours 2.30%
5(a) Faults per 100 circuit-km of electric line:
| 2003 | 2002 | 2001 | 2000 | |
|---|---|---|---|---|
| 66kV | 4.4 | 2.9 | 0.0 | 1.7 |
| 33kV | 3.9 | 3.7 | 2.8 | 4.3 |
| 11kV | 11.6 | 7.7 | 9.7 | 10.0 |
| All | 10.9 | 7.3 | 9.1 | 9.5 |
(b) & (c) Target number of faults per 100 circuit-km of electric line:
| 2004 | Average 2004 - 2008 | |
|---|---|---|
| 66kV | 2.0 | 2.0 |
| 33kV | 4.0 | 4.0 |
| 11kV | 12.0 | 12.0 |
| All | 11.2 | 11.2 |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2003, No 103
Gazette.govt.nz —
NZ Gazette 2003, No 103
β¨ LLM interpretation of page content
πΎ
Disclosure of Reliability Performance Measures by Line Owners
(continued from previous page)
πΎ Primary Industries & ResourcesElectricity, Reliability performance, Interruptions, Faults, Orion, Transpower