β¨ Electricity Reliability Statistics
ELECTRICITY INVERCARGILL LIMITED LINE BUSINESS
RELIABILITY PERFORMANCE MEASURES
PURSUANT TO REGULATION 22 OF THE ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1999 AS AMENDED BY THE ELECTRICITY (INFORMATION DISCLOSURE) AMENDMENT REGULATIONS 2000
Reliability Statistics For Years Ending 31 March 1999, 2000, 2001 and 2002
| Class | A | B | C | D | E | F | G | TOTAL |
|---|---|---|---|---|---|---|---|---|
| Interruptions | ||||||||
| 1998/99 | - | 16 | 36 | 1 | - | - | 1 | 54 |
| 1999/00 | - | 18 | 22 | - | - | - | - | 40 |
| 2000/01 | - | 11 | 29 | - | - | - | - | 40 |
| 2001/02 | - | 11 | 22 | 2 | - | - | - | 35 |
| Predicted 2002/2003 | - | 10 | 23 | - | - | - | - | 33 |
| 5-Year Average Target | - | 9 | 21 | - | - | - | - | 30 |
| SAIDI | | | | | | | | |
| 1998/99 | - | 7.7 | 43.4| 51.6| - | - | 1.3 | 104.0 |
| 1999/00 | - | 4.7 | 29.0| - | - | - | - | 33.7 |
| 2000/01 | - | 4.0 | 31.0| - | - | - | - | 35.0 |
| 2001/02 | - | 4.0 | 32.0| 59.8| - | - | - | 95.8 |
| Predicted 2002/2003| - | 3.6 | 28.2| - | - | - | - | 31.8 |
| 5-Year Average Target | - | 3.2 | 25.7| - | - | - | - | 28.9 |
| SAIFI | | | | | | | | |
| 1998/99 | - | 0.07| 1.27| 1.01| 0.06| - | - | 2.41 |
| 1999/00 | - | 0.11| 0.53| - | - | - | - | 0.64 |
| 2000/01 | - | 0.05| 1.07| - | - | - | - | 1.12 |
| 2001/02 | - | 0.04| 1.12| 1.71| - | - | - | 2.87 |
| Predicted 2002/2003| - | 0.04| 1.01| - | - | - | - | 1.05 |
| 5-Year Average Target | - | 0.04| 0.92| - | - | - | - | 0.96 |
| CAIDI | | | | | | | | |
| 1998/99 | - | 110.3| 34.1| 51.0| - | - | 22.0| 43.1 |
| 1999/00 | - | 42.5| 54.8| - | - | - | - | 52.7 |
| 2000/01 | - | 80.4| 28.9| - | - | - | - | 31.2 |
| 2001/02 | - | 98.8| 28.5| 35.0| - | - | - | 33.3 |
| Predicted 2002/2003| - | 89.0| 28.0| - | - | - | - | 30.4 |
| 5-Year Average Target | - | 88.0| 28.0| - | - | - | - | 30.3 |
Faults by Voltage
| Faults by Voltage | 66kV | 33kV | 11kV | Total |
|---|---|---|---|---|
| OH per 100km | ||||
| 1998/99 | - | - | 48.9 | 48.7 |
| 1999/00 | - | - | 17.9 | 17.9 |
| 2000/01 | - | - | 38.8 | 38.6 |
| 2001/02 | - | - | 37.6 | 36.9 |
| UG per 100km |
| 1998/99 | - | - | 2.5 | 2.2 |
| 1999/00 | - | - | 4.8 | 4.2 |
| 2000/01 | - | - | 5.4 | 4.7 |
| 2001/02 | - | - | 4.4 | 3.8 |
| Total per 100km |
| 1998/99 | - | - | 2.5 | 2.2 |
| 1999/00 | - | - | 4.8 | 4.2 |
| 2000/01 | - | - | 5.4 | 4.7 |
| 2001/02 | - | - | 12.2 | 10.8 |
| Predicted 2002/2003 | - | - | 12.2 | 10.8 |
| 5-Year Average Target | - | - | 11.1 | 9.8 |
Class C Interruptions Not Restored in 3 hours: Nil
Class C Interruptions Not Restored in 24 hours: Nil
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2002, No 91
Gazette.govt.nz —
NZ Gazette 2002, No 91
β¨ LLM interpretation of page content
ποΈ
Reliability Performance Measures for Electricity Invercargill Limited Line Business
(continued from previous page)
ποΈ Infrastructure & Public WorksElectricity, Reliability Statistics, Interruptions, SAIDI, SAIFI, CAIDI, Faults by Voltage, Invercargill