24 JUNE
NEW ZEALAND GAZETTE
1869

6.6 kV system

2002 2001 2000 1999
0.00 0.00 0.00 0.00

Average number of faults targeted (5 years)

2003/07 2002/06 2001/05 2000/04
33 kV system 1.50 1.50 1.50 6.00
11 kV system 5.00 6.30 6.30 4.00
6.6 kV system 0.00 0.00 0.00 0.00
  1. Number of faults per 100km of prescribed voltage underground line
2002 2001 2000 1999
33 kV system 0.00 0.00 52.63 28.65
11 kV system 2.47 8.31 3.51 10.86
6.6 kV system 0.00 0.00 0.00 0.00
Total 2.34 7.86 5.04 11.28
  1. Number of faults per 100km of prescribed voltage overhead line
2002 2001 2000 1999
33 kV system 1.67 1.67 1.65 9.08
11 kV system 4.28 5.21 6.23 6.24
6.6 kV system 0.00 9.09 0.00 0.00
Total 4.06 5.06 5.85 6.31
  1. SAIDI for the total number of interruptions
2002 2001 2000 1999
114.68 172.57 215.00 340.20
  1. SAIDI targets (next year)

(a) Planned Interruptions by Line Owner (Class B)

2002/03 2001/02 2000/01 1999/00
35.00 40.00 75.00 86.00

(b) Unplanned Interruptions by Line Owner (Class C)

2002/03 2001/02 2000/01 1999/00
60.00 90.00 134.00 146.00
  1. Average SAIDI targets (5 years)

(a) Planned Interruptions by Line Owner (Class B)

2003/07 2002/06 2001/05 2000/04
32.00 35.00 56.00 65.00

(b) Unplanned Interruptions by Line Owner (Class C)

2003/07 2002/06 2001/05 2000/04
55.00 77.00 111.80 122.00
  1. Classification of SAIDI interruptions by Class

| Class A Transpower Planned | 43.92 | 67.28 | 19.00 | 58.27 |
| Class B Line Owner Planned | 21.39 | 34.86 | 62.00 | 80.59 |
| Class C Line Owner Unplanned | 49.37 | 70.14 | 122.00 | 188.72 |
| Class D Transpower Unplanned | 0.00 | 0.29 | 12.00 | 14.62 |
| Total | 114.68 | 172.57 | 215.00 | 340.20 |

  1. SAIFI for the total number of interruptions
2002 2001 2000 1999
1.14 1.92 2.94 4.51
  1. SAIFI targets (next year)

(a) Planned Interruptions

2002/03 2001/02 2000/01 1999/00
0.25 0.29 0.54 0.61

(b) Unplanned Interruptions

2002/03 2001/02 2000/01 1999/00
1.33 1.50 2.23 2.43
  1. Average SAIFI targets (5 years)

(a) Planned Interruptions by Line Owner (Class B)

2003/07 2002/06 2001/05 2000/04
0.23 0.25 0.40 0.00

(b) Unplanned Interruptions by Line Owner (Class C)

2003/07 2002/06 2001/05 2000/04
1.00 1.29 1.86 2.00
  1. Classification of SAIFI interruptions by Class

| Class A Transpower Planned | 0.14 | 0.23 | 0.05 | 0.22 |
| Class B Line Owner Planned | 0.13 | 0.29 | 0.65 | 0.57 |
| Class C Line Owner Unplanned | 0.87 | 1.34 | 2.01 | 3.22 |
| Class D Transpower Unplanned | 0.00 | 0.06 | 0.23 | 0.50 |
| Total | 1.14 | 1.92 | 2.94 | 4.51 |

  1. CAIDI for the total number of interruptions
2002 2001 2000 1999
100.59 90.27 73.00 75.43


Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2002, No 69


Gazette.govt.nz PDF NZ Gazette 2002, No 69





✨ LLM interpretation of page content

🏭 Network Tasman Limited Line Business Performance Measures (continued from previous page)

🏭 Trade, Customs & Industry
Performance Measures, Financial Performance, Efficiency Performance, Energy Delivery Efficiency, Network Tasman Limited