β¨ Electricity Reliability Statistics
THE POWER COMPANY LIMITED LINE BUSINESS
RELIABILITY PERFORMANCE MEASURES
PURSUANT TO REGULATION 22 OF THE ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1999 AS AMENDED BY THE ELECTRICITY (INFORMATION DISCLOSURE) AMENDMENT REGULATIONS 2000
RELIABILITY STATISTICS FOR YEARS ENDING 31 MARCH 1999, 2000, 2001 AND 2002
Class
A
B
C
D
E
F
G
TOTAL
1998/99
0
466
486
0
0
0
0
953
1999/00
0
424
488
1
0
1
2
916
2000/01
0
177
389
0
0
2
0
568
2001/02
0
194
375
0
0
1
0
570
Predicted 2002/2003
180
371
551
5-Year Average Target
177
365
542
SAIDI
Class
A
B
C
D
E
F
G
TOTAL
1998/99
0
60.9
276.5
17.3
0
0
0
354.7
1999/00
0
73.9
339.6
51.3
0
1.1
0
466.4
2000/01
0
16.0
130.0
0
0
0.5
0
146.5
2001/02
0
20.0
117.8
0
0
1.3
0
139.0
Predicted 2002/2003
17.2
116.0
133.2
5-Year Average Target
16.9
114.1
131.0
SAIFI
Class
A
B
C
D
E
F
G
TOTAL
1998/99
0
0.55
5.49
0.34
0
0
0
6.38
1999/00
0
0.56
5.89
0.28
0
0.04
0.01
6.78
2000/01
0
0.13
2.76
0
0
0.01
0
2.90
2001/02
0
0.14
2.73
0
0
0.01
0
2.88
Predicted 2002/2003
0.13
2.64
2.77
5-Year Average Target
0.13
2.59
2.72
CAIDI
Class
A
B
C
D
E
F
G
TOTAL
1998/99
0
110.6
50.4
51.0
0
0
0
55.6
1999/00
0
131.9
57.7
180.9
0
30.0
44.4
68.8
2000/01
0
120.5
47.1
0
0
80.0
0
50.5
2001/02
0
146.8
43.1
0
0
161.0
0
48.3
Predicted 2002/2003
132.0
44.0
48.1
5-Year Average Target
132.0
44.0
48.1
Faults by Voltage
66kV
33kV
11kV
Total
1998/99
3.17
3.13
7.49
7.02
1999/00
2.33
6.20
7.84
7.44
2000/01
1.52
2.60
6.52
5.99
2001/02
2.31
1.15
6.27
5.68
OH per 100km
66kV
33kV
11kV
Total
1998/99
3.17
3.13
7.47
7.00
1999/00
2.33
6.18
7.85
7.45
2000/01
1.52
2.59
6.54
6.00
2001/02
2.31
1.14
6.24
5.65
Predicted 2002/2003
1.70
1.90
6.20
5.60
5-Year Average Target
1.70
1.90
6.10
5.52
UG per 100km
66kV
33kV
11kV
Total
1998/99
0
0
4.40
4.26
1999/00
0
0
8.50
8.25
2000/01
0
0
8.13
7.82
2001/02
0
0
1.93
1.86
Class C Interruptions Not Restored in
3 hours: 2.7%
24 hours: 0%
Next Page →