β¨ Energy Company Performance Statistics
TOP ENERGY LIMITED
Performance Measures and Statistics
For the Year Ended 31 March 2001
Regulation 25
Reliability Performance Measures
i. Total number of interruptions and breakdowns by interruption class
| Class Type of Interruption |
5 Yr Average |
Target 2002 |
2001 |
2000 |
1999 |
1998 |
| A Planned - Transpower |
|
|
0 No |
2 No |
0 No |
0 No |
| B Planned - Top Energy |
220 |
230 |
218 |
295 |
278 |
363 |
| C Unplanned - Top Energy |
206 |
220 |
235 |
192 |
250 |
133 |
| D Unplanned - Transpower |
|
|
0 |
7 |
0 |
0 |
| E Unplanned - Embedded Generation |
|
|
0 |
0 |
0 |
0 |
| F Unplanned - Other Generation |
|
|
0 |
0 |
0 |
0 |
| G Unplanned - Another Line owner |
|
|
0 |
0 |
0 |
0 |
| H Planned - Another Line owner |
|
|
0 |
0 |
0 |
0 |
| I Any other interruption |
|
|
0 |
0 |
0 |
0 |
| Total - All interruptions |
|
|
453 |
499 |
535 |
496 |
Class C Interruptions not restored:
- a Within 3 hours: 27%
- b Within 24 hours: 0%
ii. Number of faults per 100 circuit kms
| Line Voltage |
Total |
|
|
Underground |
|
|
Overhead |
|
|
|
2001 |
2000 |
1999 |
1998 |
2001 |
2000 |
1999 |
1998 |
2001 |
| -------------- |
------- |
------ |
------ |
------ |
------- |
------ |
------ |
------ |
------- |
| 100kV |
|
|
|
|
|
|
|
|
|
| 66kV |
|
|
|
|
|
|
|
|
|
| 33kV |
4.08 |
3.67 |
4.18 |
4.18 |
0 |
0 |
0 |
0 |
4.08 |
| 11kV |
7.34 |
5.86 |
7.75 |
3.99 |
1.67 |
1.86 |
0 |
0 |
7.25 |
| 6.6kV |
|
|
|
|
|
|
|
|
|
| 3.3kV |
|
|
|
|
|
|
|
|
|
| Total |
6.92 |
5.7 |
7.49 |
4.00 |
1.67 |
1.86 |
0 |
0 |
7.01 |
| Target Faults: |
5 Yr Average |
Target 2002 |
| 33kV |
3.8 |
3.8 |
| 11kV |
5.9 |
5.9 |
| Total |
5.7 |
5.8 |
| ----------------- |
--------------- |
------------- |
|
Underground |
|
| ----------------- |
--------------- |
------------- |
| 33kV |
0 |
0 |
| 11kV |
0.7 |
1 |
| Total |
0.7 |
1 |
| ----------------- |
--------------- |
------------- |
|
Overhead |
|
| ----------------- |
--------------- |
------------- |
| 33kV |
3.8 |
3.8 |
| 11kV |
5.9 |
5.9 |
| Total |
5.8 |
5.8 |
iii. Breakdown of statistics by interruption class
| Class Type of Interruption |
SAIDI (Minutes) |
|
SAIFI (Interruptions) |
|
CAIDI (Minutes) |
|
2001 |
2000 |
1999 |
1998 |
2001 |
| ------------------------------------- |
------- |
------ |
------- |
------- |
------ |
| A Planned - Transpower |
0 |
35 |
0 |
0 |
0 |
| B Planned - Top Energy |
83 |
185 |
163 |
189 |
0.6 |
| C Unplanned - Top Energy |
246 |
275 |
574 |
243 |
4.7 |
| D Unplanned - Transpower |
0 |
0 |
391 |
0 |
0 |
| E Unplanned - Embedded Generation |
0 |
0 |
0 |
0 |
0 |
| F Unplanned - Other Generation |
0 |
0 |
0 |
0 |
0 |
| G Unplanned - Another Line owner |
0 |
0 |
0 |
0 |
0 |
| H Planned - Another Line owner |
0 |
0 |
0 |
0 |
0 |
| I Any other interruption |
0 |
0 |
0 |
0 |
0 |
| Total - All interruptions |
329 |
495 |
1128 |
432 |
5.3 |
| Targets: |
5 Yr Average |
Target 2001 |
| B Planned - Top Energy |
100 |
100 |
| C Unplanned - Top Energy |
250 |
250 |
|
SAIFI |
|
| --------------------------------------- |
-------------- |
------------- |
| B Planned - Top Energy |
6.0 |
1.0 |
| C Unplanned - Top Energy |
4.4 |
5.0 |
|
CAIDI |
|
| --------------------------------------- |
-------------- |
------------- |
| B Planned - Top Energy |
166 |
100 |
| C Unplanned - Top Energy |
56 |
50 |