✨ Electricity Reliability Statistics




OTAGO POWER LIMITED LINE BUSINESS

RELIABILITY PERFORMANCE MEASURES

PURSUANT TO REGULATION 22 OF THE ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1999 AS AMENDED BY THE ELECTRICITY (INFORMATION DISCLOSURE) AMENDMENT REGULATIONS 2000

Reliability Statistics For Years Ending 31 March 1998, 1999, 2000 and 2001

Class A B C D E F G TOTAL
1997/98 0 153 289 0 0 0 0 442
1998/99 1 184 291 4 0 0 0 480
1999/00 1 87 236 2 0 0 0 326
2000/01 2 107 216 3 0 0 0 328
Predicted 2001/2002 82 211
5-Year Average Target 73 186
SAIDI A B C D E F G TOTAL
1997/98 0 157.4 295.6 0 0 0 0 453.0
1998/99 64.8 119.8 220.8 88.1 0 0 0 493.5
1999/00 19.2 143.6 177.2 19.6 0 0 0 359.6
2000/01 125.9 64.0 133.4 8.9 0 0 0 332.2
Predicted 2001/2002 102.0 170.0
5-Year Average Target 88.8 146.9
SAIFI A B C D E F G TOTAL
1997/98 0 1.16 2.20 0 0 0 0 3.36
1998/99 0.22 0.87 1.58 0.86 0 0 0 3.53
1999/00 0.21 0.65 1.97 0.84 0 0 0 3.67
2000/01 0.43 0.48 1.95 0.26 0 0 0 3.12
Predicted 2001/2002 0.60 1.90
5-Year Average Target 0.60 1.65
CAIDI A B C D E F G TOTAL
1997/98 34.4 0 135.7 134.4 0 0 0 134.8
1998/99 294.5 137.7 139.7 102.4 0 0 0 139.8
1999/00 91.3 221.0 89.9 23.4 0 0 0 98.0
2000/01 292.7 133.4 68.4 34.4 0 0 0 106.5
Predicted 2001/2002 170.0 89.5
5-Year Average Target 148.0 89.0

Faults by Voltage

66kV 33kV 11kV Total
1997/98
OH per 100km 0 2.00 13.00 10.21
1998/99 0 3.00 15.00 13.19
1999/00 0 2.00 7.00 6.22
2000/01 0 2.27 6.58 5.85
66kV 33kV 11kV Total
1997/98
UG per 100km 0 0 0 0
1998/99 0 0 0 0
1999/00 0 0 0 0
2000/01 0 0 0 0
Total per 100km 66kV 33kV 11kV Total
1997/98 0 2.00 12.98 10.24
1998/99 0 3.00 14.98 13.16
1999/00 0 2.00 6.98 6.21
2000/01 0 2.27 6.57 5.84
Predicted 2001/2002 0 2.10 6.30 5.50
5-Year Average Target 0 1.90 5.50 4.91

Class C Interruptions Not Restored in | 3 hours | 12.5% |
Class C Interruptions Not Restored in | 24 hours | 0 |

LexisNexis



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 2001, No 96


Gazette.govt.nz PDF NZ Gazette 2001, No 96





✨ LLM interpretation of page content

πŸ’° Otago Power Limited Line Business Reliability Performance Measures (continued from previous page)

πŸ’° Finance & Revenue
Reliability Statistics, SAIDI, SAIFI, CAIDI, Faults by Voltage, Electricity