β¨ Electricity Reliability Statistics
NEW ZEALAND GAZETTE
No. 92
8 SAIDI for total of interruptions during :
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| SAIDI | 528.9 | 472.8 | 588.9 | 662.2 |
9 SAIDI targets for the following year
10 and for the subsequent four financial years
| 2002 | 2003 | 2004 | 2005 | 2006 | Average 2002/06 | |
|---|---|---|---|---|---|---|
| Planned (TLC) | 156.5 | 140.9 | 126.8 | 114.1 | 102.7 | 121.1 |
| Unplanned (TLC) | 160.3 | 144.3 | 129.8 | 116.9 | 105.2 | 124.0 |
11 SAIDI according to class
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| Planned (Transpower) | 13.3 | 0 | 0 | 0 |
| Planned (TLC) | 207.7 | 203.4 | 239.5 | 334.5 |
| Unplanned (TLC) | 321.2 | 242.4 | 329.7 | 303.8 |
| Unplanned (Transpower) | 28.0 | 27.0 | 19.7 | 23.9 |
| Generation (Others) | 3.4 | 0 | 0 | 0 |
12 SAIFI for total of interruptions during :
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| SAIFI | 5.5 | 7.34 | 8.8 | 9.3 |
13 SAIFI targets for the following year
14 and for the subsequent four financial years
| 2002 | 2003 | 2004 | 2005 | 2006 | Average 2002/06 | |
|---|---|---|---|---|---|---|
| Planned (TLC) | 0.9 | 0.7 | 0.6 | 0.5 | 0.4 | 0.6 |
| Unplanned (TLC) | 4.0 | 3.2 | 2.5 | 2.0 | 1.8 | 2.4 |
15 SAIFI according to class
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| Planned (Transpower) | 0.06 | 0 | 0 | 0 |
| Planned (TLC) | 1.12 | 0.91 | 1.25 | 1.79 |
| Unplanned (TLC) | 4.42 | 5.25 | 6.43 | 6.98 |
| Unplanned (Transpower) | 0.78 | 1.18 | 1.20 | 0.54 |
| Generation (Others) | 0.13 | 0 | 0 | 0 |
16 CAIDI for total of interruptions during :
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| CAIDI | 96.2 | 64.4 | 66.3 | 71.18 |
17 CAIDI targets for the following year
18 and for the subsequent four financial years
| 2002 | 2003 | 2004 | 2005 | 2006 | Average 2002/06 | |
|---|---|---|---|---|---|---|
| Planned (TLC) | 173.9 | 201.3 | 211.3 | 228.2 | 256.8 | 201.8 |
| Unplanned (TLC) | 40.1 | 45.1 | 51.9 | 58.5 | 58.4 | 51.7 |
19 CAIDI according to class
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| Planned (Transpower) | 240.0 | 0 | 0 | 0 |
| Planned (TLC) | 184.8 | 223.5 | 191.6 | 186.73 |
| Unplanned (TLC) | 72.7 | 46.2 | 51.3 | 43.55 |
| Unplanned (Transpower) | 35.8 | 22.9 | 16.4 | 44.54 |
| Generation (Others) | 25.5 | 0 | 0 | 0 |
PUBLISHED BY THE
DEPARTMENT OF INTERNAL AFFAIRS
PRINTED BY WICKLIFFE LIMITED
ISSN 0111-5650
Price $5.00 (inc. G.S.T.)
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2001, No 92
Gazette.govt.nz —
NZ Gazette 2001, No 92
β¨ LLM interpretation of page content
ποΈ
Reliability Performance Measures (Regulation 22)
(continued from previous page)
ποΈ Infrastructure & Public WorksElectricity, Reliability, Performance Measures, SAIDI, SAIFI, CAIDI, Interruptions, Faults