β¨ Electricity Reliability Performance Measures
DISCLOSURE OF RELIABILITY PERFORMANCE MEASURES UNDER REGULATION 22 OF THE ELECTRICITY (INFORMATION DISCLOSURE) REGULATIONS 1999
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| 1. Total Number of Interruptions | ||||
| Class A - Planned - by Transpower | 0 | 1 | 0 | 0 |
| Class B - Planned - by Line Owners | 209 | 271 | 372 | 628 |
| Class C - Unplanned - by Line Owners | 312 | 267 | 420 | 358 |
| Class D - Unplanned - by Transpower | 2 | 3 | 9 | 0 |
| Class E - Unplanned - by ECNZ | 0 | 0 | 0 | 0 |
| Class F - Unplanned - by other Generation | 0 | 0 | 0 | 0 |
| Class G - Any Other Loss of Supply | 0 | |||
| Total | 523 | 542 | 801 | 986 |
2. Interruption Targets for 2001/2002
| Class B - Planned - by Line Owners | 220 |
| Class C - Unplanned - by Line Owners| 250 |
3. Average Interruption Targets for Next 5 Yrs
| Class B - Planned - by Line Owners | 200 |
| Class C - Unplanned - by Line Owners| 200 |
4. Proportion of Class C Interruptions not restored within
| 3 Hrs | 15.7% | 13.5% | 10% |
| 24 Hrs | 0% | 0% | 0% |
5. (a) Total No. of Faults per 100 circuit kilometres of prescribed voltage electric line
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| 11 kV | 9.51 | 7.84 | 12.71 | 10.72 |
| 33 kV | 6.73 | 2.46 | 13.79 | 10.37 |
| Total | 9.34 | 7.54 | 12.77 | 10.70 |
(b) Target for 2001/2002 Year
| 11 kV | 7.70 |
| 33 kV | 1.60 |
| Total | 7.32 |
(c) Average Target for 2001/202 to 2005/2006 years
| 11 kV | <5 |
| 33 kV | <2 |
| Total | <5 |
6. Total No. of Faults per 100 circuit kilometres of underground prescribed voltage electric line
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| 11 kV | 2.56 | 2.70 | 8.00 | 6.12 |
| 33 kV | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 2.20 | 2.30 | 6.35 | 5.85 |
7. Total No. of Faults per 100 circuit kilometres of overhead prescribed voltage electric line
| 2001 | 2000 | 1999 | 1998 | |
|---|---|---|---|---|
| 11 kV | 9.69 | 7.96 | 12.78 | 10.79 |
| 33 kV | 7.18 | 2.63 | 14.74 | 11.56 |
| Total | 9.54 | 7.67 | 12.89 | 10.84 |
8. The SAIDI for the total No. of Interruptions
| | 182.52 | 131.21 | 268.25 | 240.51 |
9. SAIDI Targets for 2001/02
| Class B - Planned - by Line Owners | 35 |
| Class C - Unplanned - by Line Owners| 107 |
10. Average SAIDI Target for 2001/2 to 2005/6 Yrs
| Class B - Planned - by Line Owners | 30 |
| Class C - Unplanned - by Line Owners| 90 |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2001, No 113
Gazette.govt.nz —
NZ Gazette 2001, No 113
β¨ LLM interpretation of page content
πΎ
Disclosure of Reliability Performance Measures
(continued from previous page)
πΎ Primary Industries & ResourcesElectricity, Reliability, Performance Measures, Interruptions, Faults, SAIDI, Targets