3.3 ENERGY DELIVERY EFFICIENCY PERFORMANCE MEASURES AND STATISTICS

For the year ended 31 March 2001

Schedule 1 – PART 4 2001 2000 1999 1998

1 Energy delivery efficiency performance measures

a Load factor

58.88% | 58.87% | 59.94% | 55.70%

a/bc * 100 where

a = kWh of electricity entering system

7,120,433,531 | 6,864,048,000 | 6,681,341,709 | 3,607,989,950

b = maximum demand

1,380,517 | 1,327,434 | 1,272,484 | 657,584

c = total number of hours in financial year

8,760 | 8,784 | 8,760 | 9,851

b Loss ratio

5.34% | 4.50% | 5.44% | 6.20%

a/b * 100 where

a = losses of electricity in kWh

380,164,078 | 309,179,016 | 363,708,921 | 223,695,377

b = kWh of electricity entering system

7,120,433,531 | 6,864,048,000 | 6,681,341,709 | 3,607,989,950

c Capacity utilisation

37.25% | 35.54% | 34.03% | 39.63%

a/b * 100 where

a = maximum demand

1,380,517 | 1,327,434 | 1,272,484 | 657,584

b = transformer capacity (kVA)

3,705,855 | 3,735,466 | 3,739,313 | 1,659,135