B. RELIABILITY PERFORMANCE MEASURES (1999 REGULATIONS)
B1. Total number of interruptions, together with a breakdown of that total according to interruption class.
| Interruption Class | Number of Interruptions | |||
|---|---|---|---|---|
| 2000 | 1999 | 1998 | 1997 | |
| MainPower | ||||
| Planned Shut-Down (Class B) | 106 | 111 | 180 | 194 |
| Unplanned Interruption (Class C) | 189 | 143 | 553 | 552 |
| Trans Power | ||||
| Planned Shut-Down (Class A) | 1 | 1 | - | 1 |
| Unplanned Interruption (Class D) | 1 | - | - | 7 |
| Generation ECNZ | ||||
| Unplanned Interruption (Class E) | - | - | - | - |
| Generation Other | ||||
| Unplanned Interruption (Class F) | - | - | - | - |
| Other | ||||
| Other Interruptions (Class G) | - | - | - | - |
| Unplanned Interruption (Class G) | - | - | - | - |
| Total Interruptions | 297 | 255 | 733 | 754 |
B2. The total number of faults per 100 circuit kilometres of prescribed voltage electric line.
5.51 faults 4.27 faults 16.62 Faults 16.54 Faults
B3. The total number of faults per 100 circuit kilometres of underground prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.
| Nominal Voltage | Faults per 100 km | |||
|---|---|---|---|---|
| 2000 | 1999 | 1998 | 1997 | |
| 33 kV | - | - | 43.80 | 48.85 |
| 11 kV | 7.89 | 1.17 | 8.88 | 10.66 |
| TOTAL | 7.69 | 1.14 | 9.87 | 11.68 |
B4. The total number of faults per 100 circuit kilometres of overhead prescribed voltage electric line, together with a breakdown of that total according to different nominal line voltages.
| Nominal Voltage | Faults per 100 km | |||
|---|---|---|---|---|
| 2000 | 1999 | 1998 | 1997 | |
| 33 kV | 0.75 | 3.35 | 11.71 | 6.98 |
| 11 kV | 5.86 | 4.40 | 17.14 | 17.37 |
| TOTAL | 5.45 | 4.31 | 16.73 | 16.60 |
B5. The SAIDI for the total of interruptions:
116.94 204.71 225.05 281.85
B6. The SAIDI for the total number of interruptions within each interruption class:
| Network or Generation Owner | Classification | Minutes per Connected Customer | |||
|---|---|---|---|---|---|
| 2000 | 1999 | 1998 | 1997 | ||
| MainPower | Planned Shut-Down (Class B) | 22.06 | 86.98 | 50.00 | 61.32 |
| Unplanned Interruption (Class C) | 71.55 | 103.27 | 175.05 | 130.28 | |
| Trans Power | Planned Shut-Down (Class A) | 22.27 | 14.46 | - | 17.47 |
| Unplanned Interruption (Class D) | 1.06 | - | - | 72.77 | |
| Generation ECNZ | Unplanned Interruption (Class E) | - | - | - | - |
| Generation Other | Unplanned Interruption (Class F) | - | - | - | - |
| Other | Other Interruptions (Class G) | - | - | - | - |
| Unplanned Interruption (Class G) | - | - | - | - |
B7. The SAIFI for the total number of interruptions:
1.77 1.83 3.68 4.38
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2000, No 119
Gazette.govt.nz —
NZ Gazette 2000, No 119
β¨ LLM interpretation of page content
ποΈ
Disclosure of Reliability Performance Measures by MainPower New Zealand Ltd
(continued from previous page)
ποΈ Infrastructure & Public WorksElectricity, Reliability, Performance Measures, Faults, Interruptions, MainPower New Zealand Ltd