β¨ Electricity Reliability Performance Measures
NEW ZEALAND GAZETTE
No. 109
REGULATION 22
RELIABILITY PERFORMANCE MEASURES
for the Year Ending 31 March 2000
| 2000 | 1999 | 1998 | 1997 |
|---|
-
Total Interruptions
a) Planned Interruptions (Class B) | 342 | 492 | 401 | 372 |
b) Unplanned Interruptions (Class C) | 152 | 243 | 278 | 303 |
Total | 494 | 735 | 680 | 675 | -
Next Year Target
a) Planned Interruptions (Class B) | 400 |
b) Unplanned Interruptions (Class C) | 200 | -
Next 5 Year Average Target
a) Planned Interruptions (Class B) | 400 |
b) Unplanned Interruptions (Class C) | 200 | -
Unplanned Interruptions not restored within:
a) 3 Hours (%) | 20 | 27 | 30 | 30 |
b) 24 Hours (%) | NIL | 0 | 0 | 0 | -
Faults/100km
a) Total No. of faults | 5.98 | 10.07 | 11.58 | 12.74 |
b) Next year targets | 8 | 9.3 | - | - |
c) Next 5 year average target | 7 | 9.1 | - | - |
d) 33kV Line Voltage
i) Total no. of faults | 1.9 | 4.3 | 6.91 | 6.91 |
Next year target | 3.5 | 3.5 | - | - |
Next 5 year target | 3.0 | 3.0 | - | - |
ii) 11kV Line Voltage
a) Total no. of faults | 6.45 | 10.77 | 12.11 | 13.36 |
b) Next year target | 8 | 10 | - | - |
c) Next 5 year target | 8 | 9.9 | - | - | -
Faults/100km of Underground Line
a) Total | 14.56 | 12.14 | 16.81 | 18.56 |
b) 33kV | 0 | 0 | 36.84 | 10.53 |
c) 11kV | 15.27 | 12.88 | 15.63 | 19.05 | -
Faults/100km of Overhead Line
a) Total | 4.55 | 9.73 | 10.72 | 11.74 |
b) 33kV | 2.03 | 4.39 | 4.41 | 6.61 |
c) 11kV | 4.87 | 10.39 | 11.50 | 12.38 | -
TOTAL SAIDI | 103.99 | 162.4 | 167.18 | 164.4 |
-
SAIDI Targets Next Year
a) Planned Interruptions (Class B) | 60 |
b) Unplanned Interruptions (Class C) | 80 | -
SAIDI Targets Next 5 years
a) Planned Interruptions (Class B) | 50 |
b) Unplanned Interruptions (Class C) | 70 | -
SAIDI
a) Planned Interruptions (Class B) | 56.6 | 80.47 | 67.96 | 49.36 |
b) Unplanned Interruptions (Class C) | 47.3 | 81.96 | 95.81 | 115.05 | -
TOTAL SAIFI | 1.48 | 2.38 | 3.11 | 3.13 |
-
SAIFI Target Next Year
a) Planned Interruptions (Class B) | 0.5 |
b) Unplanned Interruptions (Class C) | 2 | -
SAIFI Target next 5 years
a) Planned Interruptions (Class B) | 0.42 |
b) Unplanned Interruptions (Class C) | 1.8 |
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 2000, No 109
Gazette.govt.nz —
NZ Gazette 2000, No 109
β¨ LLM interpretation of page content
π
Annual Valuation Reconciliation Report for Hawke's Bay Network Limited
(continued from previous page)
π Trade, Customs & IndustryElectricity, Valuation, Financial report, System fixed assets, Depreciation, Revaluation, Hawke's Bay