✨ Performance Measures for Waipa Power Limited




2188

NEW ZEALAND GAZETTE

No. 92

WAIPA POWER LIMITED - LINE BUSINESS

1999 1998 1997 1996

9 SAIDI targets for 1999 / 2000
Class B - Planned - by Line Owners 69.00
Class C - Unplanned - by Line Owners 150.00

10 Average SAIDI target for 1999 / 2000 to 2003 / 2004 years
Class B - Planned - by Line Owners 57.20
Class C - Unplanned - by Line Owners 123.60

11 The SAIDI for the total number of interruptions within each interruption class
Class A - Planned - by Transpower 0.00 0.00 0.00 0.00
Class B - Planned - by Line Owners 80.81 99.97 96.26 182.90
Class C - Unplanned - by Line Owners 161.42 153.62 231.76 170.95
Class D - Unplanned - by Transpower 0.00 1.62 25.07 34.49
Class E - Unplanned - by ECNZ 0.00 0.00 0.00 0.00
Class F - Unplanned - by other generation 0.00 0.00 0.00 0.00
Class G - Any other loss of supply 0.00 0.00 0.00 0.00

12 The SAIFI for the total number of interruptions
3.24 3.39 5.78 5.06

13 SAIFI targets for 1999 / 2000
Class B - Planned - by Line Owners 0.50
Class C - Unplanned - by Line Owners 2.50

14 Average SAIFI target for 1999 / 2000 to 2003 / 2004 years
Class B - Planned - by Line Owners 0.45
Class C - Unplanned - by Line Owners 2.19

15 The SAIFI for the total number of interruptions within each interruption class
Class A - Planned - by Transpower 0.00 0.00 0.00 0.00
Class B - Planned - by Line Owners 0.58 0.61 0.54 0.97
Class C - Unplanned - by Line Owners 2.66 2.24 4.48 3.30
Class D - Unplanned - by Transpower 0.00 0.54 0.76 0.79
Class E - Unplanned - by ECNZ 0.00 0.00 0.00 0.00
Class F - Unplanned - by other generation 0.00 0.00 0.00 0.00
Class G - Any other loss of supply 0.00 0.09 0.00 0.00

16 The CAIDI for the total number of interruptions
75 75 61 77

17 CAIDI targets for 1999 / 2000
Class B - Planned - by Line Owners 138
Class C - Unplanned - by Line Owners 60

18 Average CAIDI Target for 1999 / 2000 to 2003 / 2004 years
Class B - Planned - by Line Owners 128
Class C - Unplanned - by Line Owners 56

19 The CAIDI for the total number of interruptions within each interruption class
Class A - Planned - by Transpower 0 0 0 0
Class B - Planned - by Line Owners 140 163 180 189
Class C - Unplanned - by Line Owners 61 69 52 52
Class D - Unplanned - by Transpower 0 3 33 44
Class E - Unplanned - by ECNZ 0 0 0 0
Class F - Unplanned - by other generation 0 0 0 0
Class G - Any other loss of supply 0 0 0 0



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1999, No 92


NZLII PDF NZ Gazette 1999, No 92





✨ LLM interpretation of page content

🏭 Performance Measures for Waipa Power Limited (continued from previous page)

🏭 Trade, Customs & Industry
Electricity, Performance Measures, Reliability, Interruptions, Faults, SAIDI, SAIFI, CAIDI, Line Business, Waipa Power Limited